Compare Equipment Go Back

XQ570 Tier 4 Final - 455 ekW (568 kVA)
Cat XLM Switchgear
Cat Customizable Switchgear and Controls

Generator Set

Rating Prime 455 ekW (568 kVA) - -
Frequency 60 Hz - -
Voltage 120 - 600 V - -
Rating Standby 500 ekW (625 kVA) - -

Engine

Engine Cat C18 - -
Fuel Diesel - -

Dimensions

Height - Without Trailer 102 in - -
Length - Without Trailer 240 in - -
Width - Without Trailer 96 in - -
Weight with Lube Oil and Coolant, Without Trailer 24125 lb - -

Fuel Consumption

100% Load 60Hz 35.9 gal/hr - -
75% Load 60Hz 28.3 gal/hr - -
50% Load 60Hz 20.5 gal/hr - -

Noise rating (with enclosure)

Sound Power @ 7 meters (23 feet) @ All Ratings 74 dB(A) - -

Technical Summary

Configuration - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc
Modes of Operation - Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow
Application - LV and MV ( 208V - 38 kV LV and MV ( 208V - 38 kV) 50 / 60 Hz

Generator Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 Per customer specification

Utility Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 Per customer specification

Environmental Parameters

Certifications - IBS, CBC, UBC & OSHPD Certified Per customer specification
Control Panel Enclosure - NEMA 1 or NEMA 3R, Freestanding Construction Per customer specification
Operating Temperature - 0 degrees to 50 degrees C Per customer specification
Storage Temperature - -20 degrees C to +60 degrees C Per customer specification
Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 Per customer specification
Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 Per customer specification
Add a Similar Product:
  • Cat Switchgear Add
  • Cat EGP Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • EMCP 4.4 Master Control Panel Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add
  • XQ230 Rental Power Add