XQ425
Cat EGP Switchgear

Generator Set

Rating Prime 340 ekW (425 kVA) - -
Frequency 50/60 Hz - -
Voltage 120 - 600 V - -
Rating Standby 375 ekW (469 kVA) - -

Engine

Engine C13 - -
Fuel Diesel - -

Dimensions

Height - Without Trailer 60 in - -
Length - Without Trailer 208.7 in - -
Width - Without Trailer 104 in - -
Weight with Lube Oil and Coolant, Without Trailer 14700 lb - -

Fuel Consumption

100% Load 60Hz 25.1 gal/hr - -
75% Load 60Hz 19.2 gal/hr - -
50% Load 60Hz 13.6 gal/hr - -

Noise rating (with enclosure)

Sound Power @ 7 meters (23 feet) @ All Ratings 74 dB(A) - -

Technical Summary

Configuration - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications -
Modes of Operation - Multi-unit Island and multi-unit standby mode with optional redundant controls and components. -
Application - LV and MV (208V - 38 kV) -

Generator Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 -

Environmental Parameters

Certifications - IBC, CBC, UBC & OSHPD Certified -
Control Panel Enclosure - NEMA 1 or NEMA 3R Freestanding Construction -
Operating Temperature - 0°C to 50°C -
Storage Temperature - -20°C to +60°C -
Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 -
Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 -
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Cat Switchgear Add
  • Cat XLM Switchgear Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • EMCP 4.4 Master Control Panel Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add