Compare Equipment Go Back

XQ230 Rental Power
Cat Customizable Switchgear and Controls
XQ570 Tier 4 Final - 455 ekW (568 kVA)

Generator Set

Rating Prime 182 ekW (228 kVA) - 455 ekW (568 kVA)
Frequency 60 Hz - 60 Hz
Voltage 120 - 600 V - 120 - 600 V
Rating Standby 200 ekW (250 kVA) - 500 ekW (625 kVA)

Engine

Engine Cat C7.1 - Cat C18
Fuel Diesel - Diesel

Dimensions

Height - Without Trailer 78.5 in - 102 in
Length - Without Trailer 162.2 in - 240 in
Width - Without Trailer 62.8 in - 96 in
Weight with Lube Oil and Coolant, Without Trailer 8432 lb - 24125 lb

Fuel Consumption

100% Load 60Hz 14.7 gal/hr - 35.9 gal/hr
75% Load 60Hz 10.8 gal/hr - 28.3 gal/hr
50% Load 60Hz 7.4 gal/hr - 20.5 gal/hr

Noise rating (with enclosure)

Sound Power @ 7 meters (23 feet) @ All Ratings 72 dB(A) - 74 dB(A)

Technical Summary

Configuration - Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc -
Modes of Operation - All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow -
Application - LV and MV ( 208V - 38 kV) 50 / 60 Hz -

Generator Protective Devices

ANSI Protective Devices - Per customer specification -

Utility Protective Devices

ANSI Protective Devices - Per customer specification -

Environmental Parameters

Certifications - Per customer specification -
Control Panel Enclosure - Per customer specification -
Operating Temperature - Per customer specification -
Storage Temperature - Per customer specification -
Low Voltage Standards - Per customer specification -
Medium Voltage Standards - Per customer specification -
Add a Similar Product:
  • Cat XLM Switchgear Add
  • Cat Switchgear Add
  • Cat EGP Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Temporary Connection Boxes Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • XQ425 Add