Compare Equipment Go Back
XQ125 Rental Power |
Cat XLM Switchgear |
XQ570 Tier 4 Final - 455 ekW (568 kVA) |
|
Generator Set |
|||
---|---|---|---|
Rating Prime | 100 ekW (125 kVA) | - | 455 ekW (568 kVA) |
Frequency | 60 Hz | - | 60 Hz |
Voltage | 120 - 600 V | - | 120 - 600 V |
Rating Standby | 110 ekW (137 kVA) | - | 500 ekW (625 kVA) |
Engine |
|||
Engine | Cat C4.4 | - | Cat C18 |
Fuel | Diesel | - | Diesel |
Dimensions |
|||
Height - Without Trailer | 73 in | - | 102 in |
Length - Without Trailer | 127 in | - | 240 in |
Width - Without Trailer | 49 in | - | 96 in |
Weight with Lube Oil and Coolant, Without Trailer | 5230 lb | - | 24125 lb |
Fuel Consumption |
|||
100% Load 60Hz | 8.3 gal/hr | - | 35.9 gal/hr |
75% Load 60Hz | 5.51 gal/hr | - | 28.3 gal/hr |
50% Load 60Hz | 3.8 gal/hr | - | 20.5 gal/hr |
Noise rating (with enclosure) |
|||
Sound Power @ 7 meters (23 feet) @ Prime Rating | 65 dB(A) | - | - |
Sound Power @ 7 meters (23 feet) @ Standby Rating | 66 dB(A) | - | - |
Sound Power @ 7 meters (23 feet) @ All Ratings | - | - | 74 dB(A) |
Technical Summary |
|||
Configuration | - | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications | - |
Modes of Operation | - | Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power | - |
Application | - | LV and MV ( 208V - 38 kV | - |
Generator Protective Devices |
|||
ANSI Protective Devices | - | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | - |
Utility Protective Devices |
|||
ANSI Protective Devices | - | 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 | - |
Environmental Parameters |
|||
Certifications | - | IBS, CBC, UBC & OSHPD Certified | - |
Control Panel Enclosure | - | NEMA 1 or NEMA 3R, Freestanding Construction | - |
Operating Temperature | - | 0 degrees to 50 degrees C | - |
Storage Temperature | - | -20 degrees C to +60 degrees C | - |
Low Voltage Standards | - | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | - |
Medium Voltage Standards | - | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | - |
Add a Similar Product:
- Cat Switchgear Add
- Cat Customizable Switchgear and Controls Add
- EMCP 4.4 Master Control Panel Add
- Cat EGP Switchgear Add
- Engine Paralleling and Integration Control (EPIC) Add
- Energy Capacity Expansion (ECE) module Add
- Cat® BDP1000 Bi-Directional Power Inverter Add
- Energy Time Shift (ETS) Module Add
- Temporary Connection Boxes Add
- XQP550 EU Stage V Add