Compare Equipment Go Back
XQ125 Rental Power |
Cat XLM Switchgear |
EMCP 4.4 Master Control Panel |
Cat® BDP1000 Bi-Directional Power Inverter |
|
Generator Set |
||||
---|---|---|---|---|
Rating Prime | 100 ekW (125 kVA) | - | - | - |
Frequency | 60 Hz | - | - | - |
Voltage | 120 - 600 V | - | - | - |
Rating Standby | 110 ekW (137 kVA) | - | - | - |
Engine |
||||
Engine | Cat C4.4 | - | - | - |
Fuel | Diesel | - | - | - |
Dimensions |
||||
Height - Without Trailer | 73 in | - | - | - |
Length - Without Trailer | 127 in | - | - | - |
Width - Without Trailer | 49 in | - | - | - |
Weight with Lube Oil and Coolant, Without Trailer | 5230 lb | - | - | - |
Fuel Consumption |
||||
100% Load 60Hz | 8.3 gal/hr | - | - | - |
75% Load 60Hz | 5.51 gal/hr | - | - | - |
50% Load 60Hz | 3.8 gal/hr | - | - | - |
Noise rating (with enclosure) |
||||
Sound Power @ 7 meters (23 feet) @ Prime Rating | 65 dB(A) | - | - | - |
Sound Power @ 7 meters (23 feet) @ Standby Rating | 66 dB(A) | - | - | - |
Technical Summary |
||||
Configuration | - | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications | Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source. | - |
Modes of Operation | - | Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power | Emergency standby, island, utility paralleling | - |
Application | - | LV and MV ( 208V - 38 kV | LV and MV (208V - 38 kV) | Energy Storage System |
Module Type | - | - | - | Integral part of Power Grid Stabilization and Energy Time Shift modules |
Rated Power | - | - | - | 1000 kVA (1000kW 1PF) |
Generator Protective Devices |
||||
ANSI Protective Devices | - | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | - |
Utility Protective Devices |
||||
ANSI Protective Devices | - | 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 | 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) | - |
Environmental Parameters |
||||
Certifications | - | IBS, CBC, UBC & OSHPD Certified | IBC, CBC, UBC & OSHPD Certified | - |
Control Panel Enclosure | - | NEMA 1 or NEMA 3R, Freestanding Construction | NEMA 1 wall-mounted construction | - |
Operating Temperature | - | 0 degrees to 50 degrees C | 0°C to 50°C | - |
Storage Temperature | - | -20 degrees C to +60 degrees C | -20°C to +60°C | - |
Low Voltage Standards | - | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | - |
Medium Voltage Standards | - | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | - |
Add a Similar Product:
- Cat Switchgear Add
- Cat Customizable Switchgear and Controls Add
- Cat EGP Switchgear Add
- Engine Paralleling and Integration Control (EPIC) Add
- Energy Capacity Expansion (ECE) module Add
- Energy Time Shift (ETS) Module Add
- XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
- Temporary Connection Boxes Add
- XQP550 EU Stage V Add
- XQ230 Rental Power Add