Compare Equipment Go Back

CG170-12 Gas Generator Set
Cat XLM Switchgear
Engine Paralleling and Integration Control (EPIC)

Generator Set Specifications

Continuous Rating 1200 ekW @1.0pf - -
Fuel Type Natural Gas, Biogas, Coal Gas - -
Maximum Electrical Efficiency 43.40% - -
Frequency 50 or 60 Hz - -
RPM 1500 rpm - -

Engine Specifications

Engine Model CG170-12 - -
Displacement 3240 in³ - -
Aspiration TA - -
Bore 6.7 in - -
Stroke 7.7 in - -

Generator Set Dimensions

Length 235 in - -
Width 70 in - -
Height 87 in - -
Dry Weight - Genset 28659.8 lb - -

Technical Summary

Configuration - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
Modes of Operation - Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Application - LV and MV ( 208V - 38 kV LV and MV (208V-27kV)

Generator Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)

Utility Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

Certifications - IBS, CBC, UBC & OSHPD Certified UL / cUL 508A
Control Panel Enclosure - NEMA 1 or NEMA 3R, Freestanding Construction NEMA 12
Operating Temperature - 0 degrees to 50 degrees C 0°C to 55°C
Storage Temperature - -20 degrees C to +60 degrees C -20°C to 60°C
Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 -
Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 -
Add a Similar Product:
  • Cat Switchgear Add
  • Cat Customizable Switchgear and Controls Add
  • EMCP 4.4 Master Control Panel Add
  • Cat EGP Switchgear Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Temporary Connection Boxes Add
  • Energy Time Shift (ETS) Module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • XQP550 EU Stage V Add