Compare Equipment Go Back
Gas Generator CG132B-16 |
Temporary Connection Boxes |
EMCP 4.4 Master Control Panel |
XQ230 Rental Power |
|
Generator Set Specifications |
||||
---|---|---|---|---|
Continuous Rating | 1000 ekW @1.0pf | - | - | - |
Fuel Type | Natural Gas, Hydrogen Blend (up to 25%) | - | - | - |
Maximum Electrical Efficiency | 41.50% | - | - | - |
Frequency | 50 Hz | - | - | - |
RPM | 1500 rpm | - | - | - |
Natural Gas Rating | 1000 | - | - | - |
Engine Specifications |
||||
Engine Model | CG132B | - | - | - |
Displacement | 2135.8 in³ | - | - | - |
Aspiration | TA | - | - | - |
Bore | 5.2 in | - | - | - |
Stroke | 6.3 in | - | - | - |
Generator Set Dimensions |
||||
Length | 165 in | - | - | - |
Width | 70 in | - | - | - |
Height | 85 in | - | - | - |
Dry Weight - Genset | 17791 lb | - | - | - |
Technical Summary |
||||
Application | - | EMERGENCY, LEGALLY REQUIRED EMERGENCY AND STANDBY | LV and MV (208V - 38 kV) | - |
Module Type | - | LUG-TO-LUG, CAMLOCK AND ENCLOSED CIRCUIT BREAKER | - | - |
Rated Power | - | 200 - 4000 AMPS | - | - |
Configuration | - | - | Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source. | - |
Modes of Operation | - | - | Emergency standby, island, utility paralleling | - |
Generator Protective Devices |
||||
ANSI Protective Devices | - | - | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | - |
Utility Protective Devices |
||||
ANSI Protective Devices | - | - | 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) | - |
Environmental Parameters |
||||
Certifications | - | - | IBC, CBC, UBC & OSHPD Certified | - |
Control Panel Enclosure | - | - | NEMA 1 wall-mounted construction | - |
Operating Temperature | - | - | 0°C to 50°C | - |
Storage Temperature | - | - | -20°C to +60°C | - |
Low Voltage Standards | - | - | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | - |
Medium Voltage Standards | - | - | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | - |
Generator Set |
||||
Rating Prime | - | - | - | 182 ekW (228 kVA) |
Frequency | - | - | - | 60 Hz |
Voltage | - | - | - | 120 - 600 V |
Rating Standby | - | - | - | 200 ekW (250 kVA) |
Engine |
||||
Engine | - | - | - | Cat C7.1 |
Fuel | - | - | - | Diesel |
Dimensions |
||||
Height - Without Trailer | - | - | - | 78.5 in |
Length - Without Trailer | - | - | - | 162.2 in |
Width - Without Trailer | - | - | - | 62.8 in |
Weight with Lube Oil and Coolant, Without Trailer | - | - | - | 8432 lb |
Fuel Consumption |
||||
100% Load 60Hz | - | - | - | 14.7 gal/hr |
75% Load 60Hz | - | - | - | 10.8 gal/hr |
50% Load 60Hz | - | - | - | 7.4 gal/hr |
Noise rating (with enclosure) |
||||
Sound Power @ 7 meters (23 feet) @ All Ratings | - | - | - | 72 dB(A) |
Add a Similar Product:
-
Cat Customizable Switchgear and Controls Add
-
Cat Switchgear Add
-
Cat XLM Switchgear Add
-
Cat EGP Switchgear Add
-
Engine Paralleling and Integration Control (EPIC) Add
-
Cat® BDP1000 Bi-Directional Power Inverter Add
-
XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
-
XQP550 EU Stage V Add
-
XQ425 Add
-