Compare Equipment Go Back

Gas Generator CG132B-16
Cat Customizable Switchgear and Controls
Engine Paralleling and Integration Control (EPIC)
Cat XLM Switchgear

Generator Set Specifications

Continuous Rating 800 kW @1.0pf - - -
Fuel Type Natural Gas, Biogas, Hydrogen Blend (up to 25%) - - -
Maximum Electrical Efficiency 43.5% / 42.6% - - -
Maximum Standby Rating 800 kW - - -
Frequency 50 / 60 Hz - - -
RPM 1500 / 1800 rpm - - -

Engine Specifications

Engine Model CG132 - - -
Displacement 2135.8 in³ - - -
Aspiration TA - - -
Bore 5.2 in - - -
Stroke 6.3 in - - -

Generator Set Dimensions

Length 165 in - - -
Width 70 in - - -
Height 85 in - - -
Dry Weight - Genset 17691 lb - - -

Technical Summary

Configuration - Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
Modes of Operation - All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application - LV and MV ( 208V - 38 kV) 50 / 60 Hz LV and MV (208V-27kV) LV and MV ( 208V - 38 kV

Generator Protective Devices

ANSI Protective Devices - Per customer specification 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices - Per customer specification 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86

Environmental Parameters

Certifications - Per customer specification UL / cUL 508A IBS, CBC, UBC & OSHPD Certified
Control Panel Enclosure - Per customer specification NEMA 12 NEMA 1 or NEMA 3R, Freestanding Construction
Operating Temperature - Per customer specification 0°C to 55°C 0 degrees to 50 degrees C
Storage Temperature - Per customer specification -20°C to 60°C -20 degrees C to +60 degrees C
Low Voltage Standards - Per customer specification - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards - Per customer specification - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
Add a Similar Product:
  • Cat Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Cat EGP Switchgear Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • Temporary Connection Boxes Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • XQP550 EU Stage V Add
  • XQ425 Add