Compare Equipment Go Back
Gas Generator CG132B-16 |
Cat EGP Switchgear |
Engine Paralleling and Integration Control (EPIC) |
|
Generator Set Specifications |
|||
---|---|---|---|
Continuous Rating | 800 kW @1.0pf | - | - |
Fuel Type | Natural Gas, Biogas, Hydrogen Blend (up to 25%) | - | - |
Maximum Electrical Efficiency | 43.5% / 42.6% | - | - |
Maximum Standby Rating | 800 kW | - | - |
Frequency | 50 / 60 Hz | - | - |
RPM | 1500 / 1800 rpm | - | - |
Engine Specifications |
|||
Engine Model | CG132 | - | - |
Displacement | 2135.8 in³ | - | - |
Aspiration | TA | - | - |
Bore | 5.2 in | - | - |
Stroke | 6.3 in | - | - |
Generator Set Dimensions |
|||
Length | 165 in | - | - |
Width | 70 in | - | - |
Height | 85 in | - | - |
Dry Weight - Genset | 17691 lb | - | - |
Technical Summary |
|||
Configuration | - | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications | Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) |
Modes of Operation | - | Multi-unit Island and multi-unit standby mode with optional redundant controls and components. | Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) |
Application | - | LV and MV (208V - 38 kV) | LV and MV (208V-27kV) |
Generator Protective Devices |
|||
ANSI Protective Devices | - | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) |
Environmental Parameters |
|||
Certifications | - | IBC, CBC, UBC & OSHPD Certified | UL / cUL 508A |
Control Panel Enclosure | - | NEMA 1 or NEMA 3R Freestanding Construction | NEMA 12 |
Operating Temperature | - | 0°C to 50°C | 0°C to 55°C |
Storage Temperature | - | -20°C to +60°C | -20°C to 60°C |
Low Voltage Standards | - | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | - |
Medium Voltage Standards | - | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | - |
Utility Protective Devices |
|||
ANSI Protective Devices | - | - | 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) |
Add a Similar Product:
- Cat Customizable Switchgear and Controls Add
- Cat Switchgear Add
- Cat XLM Switchgear Add
- EMCP 4.4 Master Control Panel Add
- Cat® BDP1000 Bi-Directional Power Inverter Add
- Energy Time Shift (ETS) Module Add
- Energy Capacity Expansion (ECE) module Add
- XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
- Temporary Connection Boxes Add
- XQ230 Rental Power Add