Compare Equipment Go Back

CG132B-12 Gas Generator Set
Engine Paralleling and Integration Control (EPIC)
Cat XLM Switchgear

Generator Set Specifications

Continuous Rating 600 kW @1.0pf - -
Fuel Type Natural Gas, Biogas, Hydrogen Blend (up to 25%) - -
Maximum Electrical Efficiency 43.3% / 42.4% - -
Maximum Standby Rating 600 kW - -
Frequency 50 / 60 Hz - -
RPM 1500 / 1800 rpm - -

Engine Specifications

Engine Model CG132 - -
Displacement 1604.9 in³ - -
Aspiration TA - -
Bore 5.2 in - -
Stroke 6.3 in - -

Generator Set Dimensions

Length 151 in - -
Width 70 in - -
Height 85 in - -
Dry Weight - Genset 15432 lb - -

Technical Summary

Configuration - Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
Modes of Operation - Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application - LV and MV (208V-27kV) LV and MV ( 208V - 38 kV

Generator Protective Devices

ANSI Protective Devices - 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices - 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86

Environmental Parameters

Certifications - UL / cUL 508A IBS, CBC, UBC & OSHPD Certified
Control Panel Enclosure - NEMA 12 NEMA 1 or NEMA 3R, Freestanding Construction
Operating Temperature - 0°C to 55°C 0 degrees to 50 degrees C
Storage Temperature - -20°C to 60°C -20 degrees C to +60 degrees C
Low Voltage Standards - - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards - - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Cat Switchgear Add
  • Cat EGP Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Temporary Connection Boxes Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • XQ425 Add
  • XQP550 EU Stage V Add
  • XQ230 Rental Power Add