Compare Equipment Go Back

CG132B-8 Gas Generator Set
Cat Customizable Switchgear and Controls
Engine Paralleling and Integration Control (EPIC)
XQ570 Tier 4 Final - 455 ekW (568 kVA)

Generator Set Specifications

Continuous Rating 400 ekW @1.0pf - - -
Fuel Type Natural Gas, Biogas, Coal Gas, Hydrogen Blend (up to 25%) - - -
Maximum Electrical Efficiency 43.1% / 42.1% - - -
Frequency 50 / 60 Hz - - -
RPM 1500 or 1800 rpm - - -

Engine Specifications

Engine Model CG132-8 - - -
Displacement 1067.9 in³ - - -
Aspiration TA - - -
Bore 5.2 in - - -
Stroke 6.3 in - - -

Generator Set Dimensions

Length 122 in - - -
Width 70 in - - -
Height 85 in - - -
Dry Weight - Genset 12610 lb - - -

Technical Summary

Configuration - Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) -
Modes of Operation - All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) -
Application - LV and MV ( 208V - 38 kV) 50 / 60 Hz LV and MV (208V-27kV) -

Generator Protective Devices

ANSI Protective Devices - Per customer specification 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) -

Utility Protective Devices

ANSI Protective Devices - Per customer specification 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) -

Environmental Parameters

Certifications - Per customer specification UL / cUL 508A -
Control Panel Enclosure - Per customer specification NEMA 12 -
Operating Temperature - Per customer specification 0°C to 55°C -
Storage Temperature - Per customer specification -20°C to 60°C -
Low Voltage Standards - Per customer specification - -
Medium Voltage Standards - Per customer specification - -

Generator Set

Rating Prime - - - 455 ekW (568 kVA)
Frequency - - - 60 Hz
Voltage - - - 120 - 600 V
Rating Standby - - - 500 ekW (625 kVA)

Engine

Engine - - - Cat C18
Fuel - - - Diesel

Dimensions

Height - Without Trailer - - - 102 in
Length - Without Trailer - - - 240 in
Width - Without Trailer - - - 96 in
Weight with Lube Oil and Coolant, Without Trailer - - - 24125 lb

Fuel Consumption

100% Load 60Hz - - - 35.9 gal/hr
75% Load 60Hz - - - 28.3 gal/hr
50% Load 60Hz - - - 20.5 gal/hr

Noise rating (with enclosure)

Sound Power @ 7 meters (23 feet) @ All Ratings - - - 74 dB(A)
Add a Similar Product:
  • Cat Switchgear Add
  • Cat XLM Switchgear Add
  • Cat EGP Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add
  • XQ230 Rental Power Add