Compare Equipment Go Back

Cat G3520H Combined Heat and Power (CHP) Solution
Cat EGP Switchgear
Cat XLM Switchgear

Generator Set Specifications

Continuous Rating 2480 ekW @ 1.0pf - -
Fuel Type Natural Gas - -
Maximum Electrical Efficiency 42.40% - -
Frequency 60 Hz - -
RPM 1500 - -

Engine Specifications

Engine Model G3520H - -
Displacement 5956 in³ - -
Aspiration TA - -
Bore 6.7 in - -
Stroke 8.5 in - -
Fuel System Electronic Fuel Control Valve - -
Governor Type ADEM™ A4 - -
Compression Ratio 11.1 - -

Generator Set Dimensions

Length 302 in - -
Width 86 in - -
Height 97 in - -
Dry Weight - Genset 54675 lb - -
Weight 168000 lb - -

Technical Summary

Configuration - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
Modes of Operation - Multi-unit Island and multi-unit standby mode with optional redundant controls and components. Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application - LV and MV (208V - 38 kV) LV and MV ( 208V - 38 kV

Generator Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Environmental Parameters

Certifications - IBC, CBC, UBC & OSHPD Certified IBS, CBC, UBC & OSHPD Certified
Control Panel Enclosure - NEMA 1 or NEMA 3R Freestanding Construction NEMA 1 or NEMA 3R, Freestanding Construction
Operating Temperature - 0°C to 50°C 0 degrees to 50 degrees C
Storage Temperature - -20°C to +60°C -20 degrees C to +60 degrees C
Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110

Utility Protective Devices

ANSI Protective Devices - - 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86
Add a Similar Product:
  • Cat Switchgear Add
  • Cat Customizable Switchgear and Controls Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • EMCP 4.4 Master Control Panel Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add