Compare Equipment Go Back

Gas Generator G3516H
Cat XLM Switchgear
Engine Paralleling and Integration Control (EPIC)

Generator Set Specifications

Continuous Rating 2027 / 2007 ekW @ 1.0pf - -
Fuel Type Natural Gas, Hydrogen Blend (up to 25%) - -
Maximum Electrical Efficiency 45.30% - -
Frequency 50 / 60 Hz - -
RPM 1500 rpm - -

Engine Specifications

Engine Model G3516H - -
Displacement 4765 in³ - -
Aspiration TA - -
Bore 6.7 in - -
Stroke 8.5 in - -
Compression Ratio 12.1 - -
Fuel System Natural Gas - -

Generator Set Dimensions

Length 291 in - -
Width 84 in - -
Height 95 in - -
Dry Weight - Genset 40384 lb - -

Technical Summary

Configuration - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
Modes of Operation - Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Application - LV and MV ( 208V - 38 kV LV and MV (208V-27kV)

Generator Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)

Utility Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

Certifications - IBS, CBC, UBC & OSHPD Certified UL / cUL 508A
Control Panel Enclosure - NEMA 1 or NEMA 3R, Freestanding Construction NEMA 12
Operating Temperature - 0 degrees to 50 degrees C 0°C to 55°C
Storage Temperature - -20 degrees C to +60 degrees C -20°C to 60°C
Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 -
Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 -
Add a Similar Product:
  • Cat Switchgear Add
  • Cat Customizable Switchgear and Controls Add
  • Cat EGP Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Capacity Expansion (ECE) module Add
  • Energy Time Shift (ETS) Module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add