Compare Equipment Go Back

Gas Generator G3516H
EMCP 4.4 Master Control Panel
Cat Customizable Switchgear and Controls

Generator Set Specifications

Continuous Rating 2027 / 2007 ekW @ 1.0pf - -
Fuel Type Natural Gas, Hydrogen Blend (up to 25%) - -
Maximum Electrical Efficiency 45.30% - -
Frequency 50 / 60 Hz - -
RPM 1500 rpm - -

Engine Specifications

Engine Model G3516H - -
Displacement 4765 in³ - -
Aspiration TA - -
Bore 6.7 in - -
Stroke 8.5 in - -
Compression Ratio 12.1 - -
Fuel System Natural Gas - -

Generator Set Dimensions

Length 291 in - -
Width 84 in - -
Height 95 in - -
Dry Weight - Genset 40384 lb - -

Technical Summary

Configuration - Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source. Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc
Modes of Operation - Emergency standby, island, utility paralleling All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow
Application - LV and MV (208V - 38 kV) LV and MV ( 208V - 38 kV) 50 / 60 Hz

Generator Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 Per customer specification

Utility Protective Devices

ANSI Protective Devices - 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) Per customer specification

Environmental Parameters

Certifications - IBC, CBC, UBC & OSHPD Certified Per customer specification
Control Panel Enclosure - NEMA 1 wall-mounted construction Per customer specification
Operating Temperature - 0°C to 50°C Per customer specification
Storage Temperature - -20°C to +60°C Per customer specification
Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 Per customer specification
Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 Per customer specification
Add a Similar Product:
  • Cat Switchgear Add
  • Cat EGP Switchgear Add
  • Cat XLM Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQ425 Add