Cat Customizable Switchgear and Controls
|
|
Engine Paralleling and Integration Control (EPIC)
|
Generator Set Specifications |
Continuous Rating |
1085 ekW |
- |
- |
- |
Fuel Type |
Natural Gas, Biogas, Coal Gas |
- |
- |
- |
Maximum Electrical Efficiency |
36.50% |
- |
- |
- |
Maximum Standby Rating |
1000 kw |
- |
- |
- |
Frequency |
50 / 60 Hz |
- |
- |
- |
RPM |
1200 / 1500 rpm |
- |
- |
- |
Engine Specifications |
Engine Model |
G3516A |
- |
- |
- |
Displacement |
4210 in³ |
- |
- |
- |
Aspiration |
TA |
- |
- |
- |
Bore |
6.7 in |
- |
- |
- |
Stroke |
7.5 in |
- |
- |
- |
Generator Set Dimensions |
Length |
193 in |
- |
- |
- |
Width |
68 in |
- |
- |
- |
Height |
76 in |
- |
- |
- |
Dry Weight - Genset |
27670 lb |
- |
- |
- |
Technical Summary |
Configuration |
- |
Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc |
- |
Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) |
Modes of Operation |
- |
All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow |
- |
Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) |
Application |
- |
LV and MV ( 208V - 38 kV) 50 / 60 Hz |
- |
LV and MV (208V-27kV) |
Generator Protective Devices |
ANSI Protective Devices |
- |
Per customer specification |
- |
15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) |
Utility Protective Devices |
ANSI Protective Devices |
- |
Per customer specification |
- |
15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) |
Environmental Parameters |
Certifications |
- |
Per customer specification |
- |
UL / cUL 508A |
Control Panel Enclosure |
- |
Per customer specification |
- |
NEMA 12 |
Operating Temperature |
- |
Per customer specification |
- |
0°C to 55°C |
Storage Temperature |
- |
Per customer specification |
- |
-20°C to 60°C |
Low Voltage Standards |
- |
Per customer specification |
- |
- |
Medium Voltage Standards |
- |
Per customer specification |
- |
- |
Generator Set |
Rating Prime |
- |
- |
550 kVA |
- |
Frequency |
- |
- |
50/60 Hz |
- |
Voltage |
- |
- |
220 - 480 V |
- |
Fuel/Emissions Strategy |
- |
- |
EU Stage V |
- |
Engine |
Engine |
- |
- |
Cat® C18 |
- |
Fuel |
- |
- |
Diesel |
- |
Dimensions |
Width |
- |
- |
80.3 in |
- |
Height |
- |
- |
90.5 in |
- |
Length |
- |
- |
213.3 in |
- |
Weight - With Lube Oil and Coolant |
- |
- |
14860 lb |
- |
Fuel Consumption |
100% Load 60 Hz |
- |
- |
34.3 gal/hr |
- |
100% Load 50 Hz |
- |
- |
33.4 gal/hr |
- |
75% Load 60 Hz |
- |
- |
26.13 gal/hr |
- |
75% Load 50 Hz |
- |
- |
24.9 gal/hr |
- |
Noise rating (with enclosure) |
Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz) |
- |
- |
79.19 |
- |