Compare Equipment Go Back
Gas Generator G3512H |
MX350 Controller |
|
|
Generator Set Specifications |
|||
---|---|---|---|
Continuous Rating | 1515 ekW / 1505 ekW @1.0pf | - | - |
Fuel Type | Natural Gas, Hydrogen Blend (up to 25%) | - | - |
Maximum Electrical Efficiency | 44.90% | - | - |
Frequency | 50 / 60 Hz | - | - |
RPM | 1500 rpm | - | - |
Engine Specifications |
|||
Engine Model | G3512H | - | - |
Displacement | 3574 in³ | - | - |
Aspiration | TA | - | - |
Bore | 6.7 in | - | - |
Stroke | 8.5 in | - | - |
Governor Type | ADEM A4 | - | - |
Generator Set Dimensions |
|||
Length | 223 in | - | - |
Width | 76 in | - | - |
Height | 91 in | - | - |
Dry Weight - Genset | 31085 lb | - | - |
Controller Specifications |
|||
Voltage Unbalance on Dropout for Source 1 and Source 2 | - | 5 to 20% of nominal | - |
Delay NeutralTransition Time Delays (DT,DW) | - | 0-10 minutes | - |
Control Power | - | 120 VAC | - |
Undervoltage Dropout for Source 1 and Source 2 | - | 75-99% of nominal | - |
Undervoltage Restore for Source 1 and Source 2 | - | 85-100% of nominal | - |
Overfrequency Dropout for Source 1 and Source 2 | - | 50.1 - 63 Hz | - |
Source Sensing | - | 120 - 690 VAC +/- 1% of nominal voltage (+/- .05 Hz, +/-.5 A) | - |
Delay for Engine Cool Down (U) | - | 0-60 minutes | - |
Underfrequency Restore for Source 1 and Source 2 | - | 45 - 59.5 Hz | - |
Load Control Relay Contacts (2) | - | 0-259 minutes | - |
Overvoltage Dropout for Source 1 and Source 2 | - | 105 - 110% of nominal | - |
Voltage Unbalance for Restore for Source 1 and Source 2 | - | 4 to 19% of nominal | - |
Storage Temperature | - | (-40˚C - 90˚C ) | - |
Underfrequency Dropout for Source 1 and Source 2 | - | 45 - 59.9 Hz | - |
Overfrequency Restore for Source 1 and Source 2 | - | 50 - 62.9 Hz | - |
Delay Transfer to Nonpreferred Source (W) | - | 0-5 minutes | - |
Operating Temperature Ambient | - | (-20˚C to 50˚C) | - |
Communications Interface - Optional | - | Serial RS-485 upt to 115.2 Kbps or TCP/IP (10/100 base-T) | - |
Overvoltage Restore for Source 1 and Source 2 | - | 103 - 108% of nominal | - |
Load Control Relay Contacts (1) | - | rated for 10A @ 24VDC or 120VAC | - |
Technical Summary |
|||
Rating Range | - | Switch Dependent | - |
Transfer Type | - | Application Dependent | - |
Switch Type | - | Application Dependent | - |
Add a Similar Product:
- MX150 Microprocessor Controller Add
- MX250 Microprocessor Controller Add
- CTSM and CTGM Series Manual Transfer Switches Add
- CTX Series Automatic Transfer Switch Add
- CTG Series Automatic Transfer Switch Add
- CTGSE & CTGDSE Series Service Rated Entrance Rated Automatic Transfer Switch Add
- CTS Series Automatic Transfer Switch Add
- CTE Series Automatic Transfer Switch Add
- Cat Switchgear Add
- Cat EGP Switchgear Add