Gas Generator G3512H |
Cat Customizable Switchgear and Controls |
Engine Paralleling and Integration Control (EPIC) |
Temporary Connection Boxes |
|
Generator Set Specifications |
||||
---|---|---|---|---|
Continuous Rating | 1515 ekW / 1505 ekW @1.0pf | - | - | - |
Fuel Type | Natural Gas, Hydrogen Blend (up to 25%) | - | - | - |
Maximum Electrical Efficiency | 44.90% | - | - | - |
Frequency | 50 / 60 Hz | - | - | - |
RPM | 1500 rpm | - | - | - |
Engine Specifications |
||||
Engine Model | G3512H | - | - | - |
Displacement | 3574 in³ | - | - | - |
Aspiration | TA | - | - | - |
Bore | 6.7 in | - | - | - |
Stroke | 8.5 in | - | - | - |
Governor Type | ADEM A4 | - | - | - |
Generator Set Dimensions |
||||
Length | 223 in | - | - | - |
Width | 76 in | - | - | - |
Height | 91 in | - | - | - |
Dry Weight - Genset | 31085 lb | - | - | - |
Technical Summary |
||||
Configuration | - | Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc | Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) | - |
Modes of Operation | - | All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow | Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) | - |
Application | - | LV and MV ( 208V - 38 kV) 50 / 60 Hz | LV and MV (208V-27kV) | EMERGENCY, LEGALLY REQUIRED EMERGENCY AND STANDBY |
Module Type | - | - | - | LUG-TO-LUG, CAMLOCK AND ENCLOSED CIRCUIT BREAKER |
Rated Power | - | - | - | 200 - 4000 AMPS |
Generator Protective Devices |
||||
ANSI Protective Devices | - | Per customer specification | 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) | - |
Utility Protective Devices |
||||
ANSI Protective Devices | - | Per customer specification | 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) | - |
Environmental Parameters |
||||
Certifications | - | Per customer specification | UL / cUL 508A | - |
Control Panel Enclosure | - | Per customer specification | NEMA 12 | - |
Operating Temperature | - | Per customer specification | 0°C to 55°C | - |
Storage Temperature | - | Per customer specification | -20°C to 60°C | - |
Low Voltage Standards | - | Per customer specification | - | - |
Medium Voltage Standards | - | Per customer specification | - | - |