Compare Equipment Go Back

G3512 1000kW Gas Generator Set
Cat Customizable Switchgear and Controls
Engine Paralleling and Integration Control (EPIC)

Generator Set Specifications

Gas Standby Rating 1000 ekW @ 0.8pf - -
Fuel Type Natural Gas, Hydrogen Blend (up to 5%) - -
Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Stationary Genset - -
RPM 1800 rpm - -
Frequency 60 Hz - -
Compression Ratio 9.7 - -
Displacement 3173 in³ - -

Engine Specifications

Engine Model G3512 - -
Displacement 3173 in³ - -
Aspiration TA - -
Bore 6.7 in - -
Stroke 7.5 in - -

Generator Set Dimensions

Length 205.7 in - -
Width 90 in - -
Height 99.4 in - -
Weight 27500 lb - -

Technical Summary

Configuration - Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
Modes of Operation - All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Application - LV and MV ( 208V - 38 kV) 50 / 60 Hz LV and MV (208V-27kV)

Generator Protective Devices

ANSI Protective Devices - Per customer specification 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)

Utility Protective Devices

ANSI Protective Devices - Per customer specification 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

Certifications - Per customer specification UL / cUL 508A
Control Panel Enclosure - Per customer specification NEMA 12
Operating Temperature - Per customer specification 0°C to 55°C
Storage Temperature - Per customer specification -20°C to 60°C
Low Voltage Standards - Per customer specification -
Medium Voltage Standards - Per customer specification -
Add a Similar Product:
  • Cat Switchgear Add
  • Cat EGP Switchgear Add
  • Cat XLM Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQ425 Add