Compare Equipment Go Back
G3512 750kW Gas Generator Set |
Cat Customizable Switchgear and Controls |
EMCP 4.4 Master Control Panel |
|
Generator Set Specifications |
|||
---|---|---|---|
Gas Standby Rating | 750 ekW @ 0.8pf | - | - |
Fuel Type | Natural Gas, Hydrogen Blend (up to 5%) | - | - |
Emissions/Fuel Strategy | U.S. EPA Certified for Non-Emergency Stationary Genset | - | - |
RPM | 1800 rpm | - | - |
Frequency | 60 Hz | - | - |
Displacement | 3173 in³ | - | - |
Engine Specifications |
|||
Engine Model | G3512 | - | - |
Displacement | 3173 in³ | - | - |
Aspiration | TA | - | - |
Bore | 6.7 in | - | - |
Stroke | 7.5 in | - | - |
Governor Type | ADEM A4 | - | - |
Generator Set Dimensions |
|||
Length | 205.7 in | - | - |
Width | 90 in | - | - |
Height | 99.4 in | - | - |
Weight | 27500 lb | - | - |
Technical Summary |
|||
Configuration | - | Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc | Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source. |
Modes of Operation | - | All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow | Emergency standby, island, utility paralleling |
Application | - | LV and MV ( 208V - 38 kV) 50 / 60 Hz | LV and MV (208V - 38 kV) |
Generator Protective Devices |
|||
ANSI Protective Devices | - | Per customer specification | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 |
Utility Protective Devices |
|||
ANSI Protective Devices | - | Per customer specification | 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) |
Environmental Parameters |
|||
Certifications | - | Per customer specification | IBC, CBC, UBC & OSHPD Certified |
Control Panel Enclosure | - | Per customer specification | NEMA 1 wall-mounted construction |
Operating Temperature | - | Per customer specification | 0°C to 50°C |
Storage Temperature | - | Per customer specification | -20°C to +60°C |
Low Voltage Standards | - | Per customer specification | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 |
Medium Voltage Standards | - | Per customer specification | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 |
Add a Similar Product:
- Cat Switchgear Add
- Cat EGP Switchgear Add
- Cat XLM Switchgear Add
- Engine Paralleling and Integration Control (EPIC) Add
- Cat® BDP1000 Bi-Directional Power Inverter Add
- Energy Time Shift (ETS) Module Add
- Energy Capacity Expansion (ECE) module Add
- Temporary Connection Boxes Add
- XQ425 Add
- XQ570 Tier 4 Final – 455 ekW (568 kVA) Add