Compare Equipment Go Back
DG450-2 (Single-phase) |
EMCP 4.4 Master Control Panel |
|
|
Generator Set Specifications |
|||
---|---|---|---|
Frequency | 60 Hz | - | - |
Natural Gas Rating | 450 ekW | - | - |
Emissions/Fuel Strategy | U.S. EPA Certified for Non-Emergency Application | - | - |
Voltage | 120/208, 120/240, 277/480, 346/600 VAC | - | - |
Displacement | 1336.42 in³ | - | - |
Fuel Type | Natural Gas | - | - |
Speed | 1800 rpm | - | - |
Engine Specifications |
|||
Engine Model | G21.9L V12, 4-Cycle, Spark -Ignited | - | - |
Fuel System | Carburetor, Down Draft | - | - |
Aspiration | Turbocharged - Aftercooled | - | - |
Governor Type | Electronic | - | - |
Bore | 5.03 in | - | - |
Stroke | 5.6 in | - | - |
Compression Ratio | 10.0:1 | - | - |
Generator Set Dimensions |
|||
Length | 154.4 in | - | - |
Width | 71 in | - | - |
Height | 67 in | - | - |
Weight | 8274 lb | - | - |
Technical Summary |
|||
Configuration | - | Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source. | - |
Modes of Operation | - | Emergency standby, island, utility paralleling | - |
Application | - | LV and MV (208V - 38 kV) | - |
Generator Protective Devices |
|||
ANSI Protective Devices | - | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | - |
Utility Protective Devices |
|||
ANSI Protective Devices | - | 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) | - |
Environmental Parameters |
|||
Certifications | - | IBC, CBC, UBC & OSHPD Certified | - |
Control Panel Enclosure | - | NEMA 1 wall-mounted construction | - |
Operating Temperature | - | 0°C to 50°C | - |
Storage Temperature | - | -20°C to +60°C | - |
Low Voltage Standards | - | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | - |
Medium Voltage Standards | - | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | - |
Add a Similar Product:
- Cat Customizable Switchgear and Controls Add
- Cat Switchgear Add
- Cat EGP Switchgear Add
- Cat XLM Switchgear Add
- Engine Paralleling and Integration Control (EPIC) Add
- Energy Time Shift (ETS) Module Add
- Energy Capacity Expansion (ECE) module Add
- Cat® BDP1000 Bi-Directional Power Inverter Add
- XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
- Temporary Connection Boxes Add