Compare Equipment Go Back

DG450-2 (Single-phase)
Cat EGP Switchgear
Engine Paralleling and Integration Control (EPIC)

Generator Set Specifications

Frequency 60 Hz - -
Natural Gas Rating 450 ekW - -
Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Application - -
Voltage 120/208, 120/240, 277/480, 346/600 VAC - -
Displacement 1336.42 in³ - -
Fuel Type Natural Gas - -
Speed 1800 rpm - -

Engine Specifications

Engine Model G21.9L V12, 4-Cycle, Spark -Ignited - -
Fuel System Carburetor, Down Draft - -
Aspiration Turbocharged - Aftercooled - -
Governor Type Electronic - -
Bore 5.03 in - -
Stroke 5.6 in - -
Compression Ratio 10.0:1 - -

Generator Set Dimensions

Length 154.4 in - -
Width 71 in - -
Height 67 in - -
Weight 8274 lb - -

Technical Summary

Configuration - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
Modes of Operation - Multi-unit Island and multi-unit standby mode with optional redundant controls and components. Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Application - LV and MV (208V - 38 kV) LV and MV (208V-27kV)

Generator Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)

Environmental Parameters

Certifications - IBC, CBC, UBC & OSHPD Certified UL / cUL 508A
Control Panel Enclosure - NEMA 1 or NEMA 3R Freestanding Construction NEMA 12
Operating Temperature - 0°C to 50°C 0°C to 55°C
Storage Temperature - -20°C to +60°C -20°C to 60°C
Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 -
Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 -

Utility Protective Devices

ANSI Protective Devices - - 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Cat Switchgear Add
  • Cat XLM Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQ425 Add