Compare Equipment Go Back

DG300-2 (3 phase)
Cat EGP Switchgear
Cat Customizable Switchgear and Controls

Generator Set Specifications

Frequency 60 Hz - -
Natural Gas Rating 300 eKW - -
Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Application - -
Displacement 864.71 in³ - -
Speed 1800 rpm - -

Engine Specifications

Engine Model 14.2 L Spark - Ignited - -
Compression Ratio 9.5:1 - -
Fuel System Electronic - -
Bore 5.31 in - -
Stroke 6.5 in - -

Generator Set Dimensions

Length 136 in - -
Width 57.6 in - -
Height 66.1 in - -
Weight 6274 lb - -

Technical Summary

Configuration - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc
Modes of Operation - Multi-unit Island and multi-unit standby mode with optional redundant controls and components. All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow
Application - LV and MV (208V - 38 kV) LV and MV ( 208V - 38 kV) 50 / 60 Hz

Generator Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 Per customer specification

Environmental Parameters

Certifications - IBC, CBC, UBC & OSHPD Certified Per customer specification
Control Panel Enclosure - NEMA 1 or NEMA 3R Freestanding Construction Per customer specification
Operating Temperature - 0°C to 50°C Per customer specification
Storage Temperature - -20°C to +60°C Per customer specification
Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 Per customer specification
Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 Per customer specification

Utility Protective Devices

ANSI Protective Devices - - Per customer specification
Add a Similar Product:
  • Cat Switchgear Add
  • Cat XLM Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • EMCP 4.4 Master Control Panel Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • Temporary Connection Boxes Add
  • XQ425 Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add