Compare Equipment Go Back

DG275-2 (3 phase)
Engine Paralleling and Integration Control (EPIC)
Cat Customizable Switchgear and Controls

Generator Set Specifications

Frequency 60 Hz - -
Natural Gas Rating 275 eKW - -
Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Application - -
Displacement 864.71 in³ - -
Speed 1800 rpm - -

Engine Specifications

Fuel System Carburetor, Down Draft - -
Compression Ratio 9.5:1 - -
Bore 5.31 in - -
Stroke 6.5 in - -

Generator Set Dimensions

Length 136 in - -
Width 57.6 in - -
Height 66.1 in - -
Weight 6274 lb - -

Technical Summary

Configuration - Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc
Modes of Operation - Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow
Application - LV and MV (208V-27kV) LV and MV ( 208V - 38 kV) 50 / 60 Hz

Generator Protective Devices

ANSI Protective Devices - 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) Per customer specification

Utility Protective Devices

ANSI Protective Devices - 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) Per customer specification

Environmental Parameters

Certifications - UL / cUL 508A Per customer specification
Control Panel Enclosure - NEMA 12 Per customer specification
Operating Temperature - 0°C to 55°C Per customer specification
Storage Temperature - -20°C to 60°C Per customer specification
Low Voltage Standards - - Per customer specification
Medium Voltage Standards - - Per customer specification
Add a Similar Product:
  • Cat Switchgear Add
  • Cat XLM Switchgear Add
  • Cat EGP Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add