Compare Equipment Go Back

DG275-2 (3 phase)
Engine Paralleling and Integration Control (EPIC)
EMCP 4.4 Master Control Panel

Generator Set Specifications

Frequency 60 Hz - -
Natural Gas Rating 275 eKW - -
Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Application - -
Displacement 864.71 in³ - -
Speed 1800 rpm - -

Engine Specifications

Fuel System Carburetor, Down Draft - -
Compression Ratio 9.5:1 - -
Bore 5.31 in - -
Stroke 6.5 in - -

Generator Set Dimensions

Length 136 in - -
Width 57.6 in - -
Height 66.1 in - -
Weight 6274 lb - -

Technical Summary

Configuration - Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source.
Modes of Operation - Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) Emergency standby, island, utility paralleling
Application - LV and MV (208V-27kV) LV and MV (208V - 38 kV)

Generator Protective Devices

ANSI Protective Devices - 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices - 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

Certifications - UL / cUL 508A IBC, CBC, UBC & OSHPD Certified
Control Panel Enclosure - NEMA 12 NEMA 1 wall-mounted construction
Operating Temperature - 0°C to 55°C 0°C to 50°C
Storage Temperature - -20°C to 60°C -20°C to +60°C
Low Voltage Standards - - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards - - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Cat Switchgear Add
  • Cat EGP Switchgear Add
  • Cat XLM Switchgear Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQ425 Add