Compare Equipment Go Back

DG175-2 (Single-phase)
Cat Customizable Switchgear and Controls
Energy Capacity Expansion (ECE) module
Engine Paralleling and Integration Control (EPIC)

Generator Set Specifications

Frequency 60 Hz - - -
Natural Gas Rating 175 ekW - - -
Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Application - - -
Displacement 864.71 in - - -
Fuel Type Natural Gas - - -
Speed 1800 rpm - - -

Engine Specifications

Engine Model G14.2L Inline 6, 4 cycle, Spark Ignited - - -
Fuel System Carburetor, Down Draft - - -
Aspiration Turbocharged - Aftercooled - - -
Governor Type Electronic - - -
Compression Ratio 9.5:1 - - -
Bore 5.31 in - - -
Stroke 6.5 in - - -

Generator Set Dimensions

Length 127.95 in - - -
Width 52.93 in - - -
Height 67.37 in - - -
Weight 5756 lb - - -

Technical Summary

Configuration - Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc - Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
Modes of Operation - All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow - Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Application - LV and MV ( 208V - 38 kV) 50 / 60 Hz Reserve Power Capacity LV and MV (208V-27kV)
Module Type - - Energy Storage -
Nameplate Energy Capacity - - 1518 kWh - 7590 kWh -

Generator Protective Devices

ANSI Protective Devices - Per customer specification - 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)

Utility Protective Devices

ANSI Protective Devices - Per customer specification - 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

Certifications - Per customer specification - UL / cUL 508A
Control Panel Enclosure - Per customer specification - NEMA 12
Operating Temperature - Per customer specification - 0°C to 55°C
Storage Temperature - Per customer specification - -20°C to 60°C
Low Voltage Standards - Per customer specification - -
Medium Voltage Standards - Per customer specification - -
Add a Similar Product:
  • Cat Switchgear Add
  • Cat XLM Switchgear Add
  • Cat EGP Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add
  • XQ230 Rental Power Add