Compare Equipment Go Back

DG175-2 (Single-phase)
Cat EGP Switchgear
Cat XLM Switchgear

Generator Set Specifications

Frequency 60 Hz - -
Natural Gas Rating 175 ekW - -
Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Application - -
Displacement 864.71 in - -
Fuel Type Natural Gas - -
Speed 1800 rpm - -

Engine Specifications

Engine Model G14.2L Inline 6, 4 cycle, Spark Ignited - -
Fuel System Carburetor, Down Draft - -
Aspiration Turbocharged - Aftercooled - -
Governor Type Electronic - -
Compression Ratio 9.5:1 - -
Bore 5.31 in - -
Stroke 6.5 in - -

Generator Set Dimensions

Length 127.95 in - -
Width 52.93 in - -
Height 67.37 in - -
Weight 5756 lb - -

Technical Summary

Configuration - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
Modes of Operation - Multi-unit Island and multi-unit standby mode with optional redundant controls and components. Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application - LV and MV (208V - 38 kV) LV and MV ( 208V - 38 kV

Generator Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Environmental Parameters

Certifications - IBC, CBC, UBC & OSHPD Certified IBS, CBC, UBC & OSHPD Certified
Control Panel Enclosure - NEMA 1 or NEMA 3R Freestanding Construction NEMA 1 or NEMA 3R, Freestanding Construction
Operating Temperature - 0°C to 50°C 0 degrees to 50 degrees C
Storage Temperature - -20°C to +60°C -20 degrees C to +60 degrees C
Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110

Utility Protective Devices

ANSI Protective Devices - - 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Cat Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • EMCP 4.4 Master Control Panel Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQ230 Rental Power Add