Compare Equipment Go Back

3616 Generator Set (Medium Speed)

Generator Set Specifications

Maximum Rating 7520 kVA 4000 ekW -
Minimum Rating 4700 kVA 3150 ekW -
Emissions/Fuel Strategy Low Fuel Consumption Low Fuel, Tier 2 -
Frequency 50 Hz 60 Hz -
Speed 720 & 1000 rpm 1800 rpm -
Duty Cycle Standby, Prime, Continuous Standby, Mission Critical, Prime, Continuous -
Standby Rating - 4000 (no fan)/3900/3620(no fan)/3500 ekW -
Prime Power Rating - 3600 (no fan)/3500/3300 (no fan)/3180 ekW -
Voltage - 480 to 13800 Volts -

Engine Specifications

Engine Model 3616 V-16, 4-Stroke Water-Cooled Diesel C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel -
Bore 11 in 6.89 in -
Stroke 11.8 in 8.66 in -
Displacement 18032 in³ 6456.31 in³ -
Compression Ratio 13:01 15.3:1 -
Aspiration TA Turbo Aftercooled -
Fuel System Direct unit injection Common Rail -
Governor Type Generator Set Monitoring System (GMS) ADEM� A4 -

Generator Set Dimensions

Length - Maximum 404 in 330.6 in -
Width - Maximum 99.62 in 127.7 in -
Height - Maximum 156.6 in 150.7 in -
Dry Weight - Genset (maximum) 141840 lb 66200 lb -
Length - Minimum - 261.5 in -
Width - Minimum - 85.4 in -
Height - Minimum - 87.6 in -
Dry Weight - Genset (minimum) - 55100 lb -
Add a Similar Product:
  • C280-16 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C280-6 Generator Set (Medium Speed) Add
  • 3606 Generator Set (Medium Speed) Add
  • 3516E Low Voltage Generator Set Add