Compare Equipment Go Back

3516E Generator Set
3616 Generator Set (Medium Speed)
C280-8 Generator Set (Medium Speed)

Generator Set Specifications

Standby Rating 3500/3250/3000 kVA - -
Prime Power Rating 3175/2950/2725 kVA - -
Emissions/Fuel Strategy U.S. EPA Cert. Tier 2 / Low NOx Low Fuel Consumption EPA Tier 4 Final, IMO Tier 2
Voltage 380 to 11000 volts - -
Frequency 50 Hz 50 Hz 50 / 60 Hz
Speed 1500 rpm 720 & 1000 rpm 900 / 1000 rpm
Duty Cycle Standby, Mission Critical, Prime Standby, Prime, Continuous Prime, Continuous
Maximum Rating 3500 kVA 7520 kVA 2420 ekW (60Hz), 3250 kVA (50Hz)
Minimum Rating 2725 kVA 4700 kVA 2200 ekW (60Hz), 2938 kVA (50Hz)

Engine Specifications

Engine Model 3516E, V-16, 4-Stroke Water-Cooled Diesel 3616 V-16, 4-Stroke Water-Cooled Diesel C280-8, I-8,4-Stroke Water-Cooled Diesel
Bore 6.69 in 11 in 11 in
Stroke 8.46 in 11.8 in 11.8 in
Displacement 4765 in³ 18032 in³ 9064 in³
Compression Ratio 14.0:1 13:01 13:01
Aspiration ATAAC TA TA
Fuel System Electronic Unit Injection Direct unit injection Direct unit injection
Governor Type Adem™ A5 Generator Set Monitoring System (GMS) Generator Set Monitoring System (GMS)

Generator Set Dimensions

Length - Minimum 302.6 in - -
Length - Maximum 306.5 in 404 in 404 in
Width - Maximum 102.8 in 99.62 in 99.62 in
Height - Maximum 131.6 in 156.6 in 156.6 in
Dry Weight - Genset (minimum) 44930 lb - -
Dry Weight - Genset (maximum) 45651 lb 141840 lb 91050 lb
Add a Similar Product:
  • C280-16 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C280-6 Generator Set (Medium Speed) Add
  • C175-20 Add
  • 3606 Generator Set (Medium Speed) Add
  • C175-16 Generator Set Add