Compare Equipment Go Back

3516B Generator Set

Generator Set Specifications

Standby Rating 2500 kVA 4000 (no fan)/3900/3620(no fan)/3500 ekW -
Prime Power Rating 2275 kVA 3600 (no fan)/3500/3300 (no fan)/3180 ekW -
Emissions/Fuel Strategy Low Fuel, Low Emissions Low Fuel, Tier 2 -
Voltage 380 to 415 Volts 480 to 13800 Volts -
Frequency 50 Hz 60 Hz -
Speed 1500 rpm 1800 rpm -
Duty Cycle Standby, Mission Critical, Prime, Continuous Standby, Mission Critical, Prime, Continuous -
Maximum Rating 2500 kVA 4000 ekW -
Minimum Rating 2000 kVA 3150 ekW -

Engine Specifications

Engine Model 3516B TA, V-16, 4-Stroke Water-Cooled Diesel C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel -
Bore 6.69 in 6.89 in -
Stroke 8.46 in 8.66 in -
Displacement 4764.73 in 6456.31 in³ -
Compression Ratio 15.5:1 15.3:1 -
Aspiration TA Turbo Aftercooled -
Fuel System Electronic unit injection Common Rail -
Governor Type Adem™3 ADEM� A4 -

Generator Set Dimensions

Length - Maximum 247.3 in 330.6 in -
Width - Maximum 90 in 127.7 in -
Height - Maximum 98.2 in 150.7 in -
Dry Weight - Genset (maximum) 34250 lb 66200 lb -
Length - Minimum - 261.5 in -
Width - Minimum - 85.4 in -
Height - Minimum - 87.6 in -
Dry Weight - Genset (minimum) - 55100 lb -
Add a Similar Product:
  • C280-16 Generator Set (Medium Speed) Add
  • 3616 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C280-6 Generator Set (Medium Speed) Add
  • 3606 Generator Set (Medium Speed) Add