Compare Equipment Go Back

3516 Diesel Generator Set
3612 Generator Set (Medium Speed)
C175-16 Tier 4 Final

Generator Set Specifications

Standby Rating 1750 ekW - 3100(no fan)/3000 ekW
Prime Power Rating 1600 ekW - 2825(no fan)/2725 ekW
Emissions/Fuel Strategy Low Fuel Consumption Low Fuel Consumption U.S. EPA Certified Tier 4
Voltage 380 to 480 Volts - 480 to 13800 Volts
Frequency 60 Hz 60 Hz 60 Hz
Speed 1800 rpm 720 & 900 rpm 1800 rpm
Duty Cycle Standby, Mission Critical, Prime, Continuous Prime, Continuous Standby, Mission Critical, Prime, Continuous
Maximum Rating 1750 ekW 4000 ekW 3100 ekW
Minimum Rating 1450 ekW 3300 ekW 2500 ekW

Engine Specifications

Engine Model 3516 TA, V-16, 4-Stroke Water-Cooled Diesel 3612 V-12,4-Stroke Water-Cooled Diesel C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel
Bore 6.69 in 11 in 6.89 in
Stroke 7.48 in 11.8 in 8.66 in
Displacement 4210.64 in³ 13524 in³ 5155.88 in³
Compression Ratio 13.5:1 13:01 16.7:1
Aspiration TA TA Turbo Aftercooled
Fuel System Mechanical unit injection Direct unit injection EUI
Governor Type Woodward Generator Set Monitoring System (GMS) ADEM� A4

Generator Set Dimensions

Length - Maximum 234.4 in 404 in 312.2 in
Width - Maximum 90 in 99.62 in 123 in
Height - Maximum 94.9 in 156.6 in 142.3 in
Dry Weight - Genset (maximum) 28840 lb 112690 lb 45114 lb
Length - Minimum - - 242.77 in
Width - Minimum - - 83.1 in
Height - Minimum - - 87 in
Dry Weight - Genset (minimum) - - 42750 lb
Add a Similar Product:
  • 3616 Generator Set (Medium Speed) Add
  • C280-16 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3606 Generator Set (Medium Speed) Add
  • C280-6 Generator Set (Medium Speed) Add
  • C175-20 Add