Compare Equipment Go Back

3512C Generator Set
3616 Generator Set (Medium Speed)
3608 Generator Set (Medium Speed)

Generator Set Specifications

Standby Rating 1750 ekW - -
Prime Power Rating 1600 ekW - -
Emissions/Fuel Strategy U.S. EPA Cert., Tier 2 Low Fuel Consumption Low Fuel Consumption
Voltage 380 to 13800 Volts - -
Frequency 60 Hz 50 Hz 50 Hz
Speed 1800 rpm 720 & 1000 rpm 750 & 1000 rpm
Duty Cycle Standby, Mission Critical Standby, Prime, Continuous Standby, Prime, Continuous
Maximum Rating 1750 ekW 7520 kVA 3575 kVA
Minimum Rating 1600 ekW 4700 kVA 2363 kVA

Engine Specifications

Engine Model 3512C ATAAC, V-12, 4-Stroke Water-Cooled Diesel 3616 V-16, 4-Stroke Water-Cooled Diesel 3608 I-8,4-Stroke Water-Cooled Diesel
Bore 6.69 in 11 in 11 in
Stroke 8.46 in 11.8 in 11.8 in
Displacement 3574 in³ 18032 in³ 9064 in³
Compression Ratio 14.7:1 13:01 13:01
Aspiration TA TA TA
Fuel System Electronic unit injection Direct unit injection Direct unit injection
Governor Type ADEM™ A3 Generator Set Monitoring System (GMS) Generator Set Monitoring System (GMS)

Generator Set Dimensions

Length - Maximum 262.9 in 404 in 404 in
Width - Maximum 89.8 in 99.62 in 99.62 in
Height - Maximum 110 in 156.6 in 156.6 in
Dry Weight - Genset (maximum) 32660 lb 141840 lb 91050 lb
Add a Similar Product:
  • C280-16 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C175-20 Add
  • 3606 Generator Set (Medium Speed) Add
  • C280-6 Generator Set (Medium Speed) Add
  • C175-16 Generator Set Add