Compare Equipment Go Back

3512B (50 Hz) Generator Set
C175-16 Tier 4 Final
3616 Generator Set (Medium Speed)

Generator Set Specifications

Standby Rating 1600/1500 kVA 3100(no fan)/3000 ekW -
Prime Power Rating 1500/1360 kVA 2825(no fan)/2725 ekW -
Emissions/Fuel Strategy Low Fuel, Low Emissions U.S. EPA Certified Tier 4 Low Fuel Consumption
Voltage 380 to 415 Volts 480 to 13800 Volts -
Frequency 50 Hz 60 Hz 50 Hz
Speed 1500 rpm 1800 rpm 720 & 1000 rpm
Duty Cycle Standby, Mission Critical, Prime Standby, Mission Critical, Prime, Continuous Standby, Prime, Continuous
Maximum Rating 1600 kVA 3100 ekW 7520 kVA
Minimum Rating 1360 kVA 2500 ekW 4700 kVA

Engine Specifications

Engine Model 3512B TA, V-12, 4-Stroke Water-Cooled Diesel C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel 3616 V-16, 4-Stroke Water-Cooled Diesel
Bore 6.69 in 6.89 in 11 in
Stroke 7.48 in 8.66 in 11.8 in
Displacement 3161.03 in³ 5155.88 in³ 18032 in³
Compression Ratio 14.0:1 16.7:1 13:01
Aspiration TA Turbo Aftercooled TA
Fuel System Electronic Unit Injection EUI Direct unit injection
Governor Type ADEM™ A3 ADEM� A4 Generator Set Monitoring System (GMS)

Generator Set Dimensions

Length - Minimum 206.6 in 242.77 in -
Length - Maximum 215.3 in 312.2 in 404 in
Width - Minimum 77.8 in 83.1 in -
Width - Maximum 90 in 123 in 99.62 in
Height - Maximum 93.2 in 142.3 in 156.6 in
Dry Weight - Genset (minimum) 25010 lb 42750 lb -
Dry Weight - Genset (maximum) 26840 lb 45114 lb 141840 lb
Height - Minimum - 87 in -
Add a Similar Product:
  • C280-12 Generator Set (Medium Speed) Add
  • C280-16 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C280-6 Generator Set (Medium Speed) Add
  • C175-20 Add
  • 3606 Generator Set (Medium Speed) Add