Compare Equipment Go Back

D600 GC (60 Hz) Generator Set
C280-6 Generator Set (Medium Speed)
3608 Generator Set (Medium Speed)

Generator Set Specifications

Maximum Rating 600 ekW 1820 ekW (60Hz), 2425 kVA (50Hz) 2660 ekW
Minimum Rating 600 ekW 1650 ekW (60Hz), 2200 kVA (50Hz) 1830 ekW
Emissions/Fuel Strategy EPA Stationary Emergency IMO Tier 2 Low Fuel Consumption
Voltage 480 to 600 Volts - -
Frequency 60 Hz 50 / 60 Hz 60 Hz
Speed 1800 rpm 900 / 1000 rpm 720 & 900 rpm
Duty Cycle Standby Prime, Continuous Standby, Prime, Continuous

Engine Specifications

Engine Model Cat® C18 In-line 6, 4-cycle Diesel C280-6, I-6,4-Stroke Water-Cooled Diesel 3608 I-8,4-Stroke Water-Cooled Diesel
Bore 5.7 in 11 in 11 in
Stroke 7.2 in 11.8 in 11.8 in
Displacement 1106 in³ 111 in³ 9064 in³
Compression Ratio 14.5:1 13:01 13:01
Aspiration Turbocharged Air-to-Air Aftercooled TA TA
Fuel System MEUI Direct unit injection Direct unit injection
Governor Type ADEM™A4 Generator Set Monitoring System (GMS) Generator Set Monitoring System (GMS)

Generator Set Dimensions

Length - Maximum 196.1 in 404 in 404 in
Width - Maximum 73.4 in 99.62 in 99.62 in
Height - Minimum 79.1 in - -
Height - Maximum 100.9 in 156.6 in 156.6 in
Dry Weight - Genset (minimum) 8959.6 lb - -
Dry Weight - Genset (maximum) 11647 lb 74970 lb 91050 lb
Add a Similar Product:
  • 3616 Generator Set (Medium Speed) Add
  • C280-16 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C175-20 Add
  • 3606 Generator Set (Medium Speed) Add
  • C175-16 Generator Set Add