Compare Equipment Go Back

C3.3 Generator Set
C175-16 Tier 4 Final

Generator Set Specifications

Maximum Rating 65.0 kVA 3100 ekW 4000 ekW
Minimum Rating 24.0 kVA 2500 ekW 3150 ekW
Emissions/Fuel Strategy EU Stage II R96/EUIIIa U.S. EPA Certified Tier 4 Low Fuel, Tier 2
Voltage 110 to 480 Volts 480 to 13800 Volts 480 to 13800 Volts
Frequency 50 Hz 60 Hz 60 Hz
Speed 1500 rpm 1800 rpm 1800 rpm
Duty Cycle Standby, Prime Standby, Mission Critical, Prime, Continuous Standby, Mission Critical, Prime, Continuous
Standby Rating - 3100(no fan)/3000 ekW 4000 (no fan)/3900/3620(no fan)/3500 ekW
Prime Power Rating - 2825(no fan)/2725 ekW 3600 (no fan)/3500/3300 (no fan)/3180 ekW

Engine Specifications

Engine Model Cat® C3.3 C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel
Bore 4.1 in 6.89 in 6.89 in
Stroke 5 in 8.66 in 8.66 in
Displacement 201.4 in³ 5155.88 in 6456.31 in³
Compression Ratio 17.25:1, 19.25:1 16.7:1 15.3:1
Aspiration Turbocharged Turbo Aftercooled Turbo Aftercooled
Fuel System Direct Injection EUI Common Rail
Governor Type Mechanical ADEM� A4 ADEM� A4

Generator Set Dimensions

Length - Maximum 43.9 in 312.2 in 330.6 in
Width - Maximum 38.2 in 123 in 127.7 in
Height - Maximum 53.6 in 142.3 in 150.7 in
Length - Minimum - 242.77 in 261.5 in
Width - Minimum - 83.1 in 85.4 in
Height - Minimum - 87 in 87.6 in
Dry Weight - Genset (minimum) - 42750 lb 55100 lb
Dry Weight - Genset (maximum) - 45114 lb 66200 lb
Add a Similar Product:
  • C280-16 Generator Set (Medium Speed) Add
  • 3616 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3606 Generator Set (Medium Speed) Add
  • C280-6 Generator Set (Medium Speed) Add