|
C32 | 1500 kVA 50Hz Generator Set
|
|
C280-12 Generator Set (Medium Speed)
|
3516E Low Voltage Generator Set
|
3608 Generator Set (Medium Speed)
|
|
Generator Set Specifications |
Maximum Rating |
1500 kVA |
4000 ekW |
3640 ekW (60Hz), 4850 kVA (50Hz) |
2750 ekW |
3575 kVA |
3100 ekW |
Minimum Rating |
910 kVA |
3150 ekW |
3300 ekW (60Hz), 4400 kVA (50Hz) |
2500 ekW |
2363 kVA |
2500 ekW |
Emissions/Fuel Strategy |
Low Fuel, Low Emissions |
Low Fuel, Tier 2 |
EPA Tier 4 Final, IMO Tier 2 |
Tier 2, Low NOx |
Low Fuel Consumption |
U.S. EPA Certified Tier 4 |
Voltage |
400 to 3300 Volts |
480 to 13800 Volts |
- |
416 to 13,800 Volts |
- |
480 to 13800 Volts |
Frequency |
50 Hz |
60 Hz |
50 / 60 Hz |
60 Hz |
50 Hz |
60 Hz |
Speed |
1500 rpm |
1800 rpm |
900 / 1000 rpm |
1800 rpm |
750 & 1000 rpm |
1800 rpm |
Duty Cycle |
Standby, Mission Critical, Prime, Continuous |
Standby, Mission Critical, Prime, Continuous |
Prime, Continuous |
Standby, Mission Critical, Prime |
Standby, Prime, Continuous |
Standby, Mission Critical, Prime, Continuous |
Standby Rating |
- |
4000 (no fan)/3900/3620(no fan)/3500 ekW |
- |
2750 ekW |
- |
3100(no fan)/3000 ekW |
Prime Power Rating |
- |
3600 (no fan)/3500/3300 (no fan)/3180 ekW |
- |
2500 ekW |
- |
2825(no fan)/2725 ekW |
Engine Specifications |
Engine Model |
C32 TA, V-12, 4-Stroke Water-Cooled Diesel |
C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel |
C280-12, V-12,4-Stroke Water-Cooled Diesel |
3516E, V-16, 4-Stroke, Water-Cooled Diesel |
3608 I-8,4-Stroke Water-Cooled Diesel |
C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel |
Bore |
5.71 in |
6.89 in |
11 in |
6.69 in |
11 in |
6.89 in |
Stroke |
6.38 in |
8.66 in |
11.8 in |
8.47 in |
11.8 in |
8.66 in |
Displacement |
1958.86 in³ |
6456.31 in³ |
13524 in³ |
4765 in³ |
9064 in³ |
5155.88 in³ |
Compression Ratio |
15.0:1 |
15.3:1 |
13:01 |
14.7:1 |
13:01 |
16.7:1 |
Aspiration |
Turbocharged, Air to Air Aftercooled |
Turbo Aftercooled |
TA |
ATAAC |
TA |
Turbo Aftercooled |
Fuel System |
MEUI |
Common Rail |
Direct unit injection |
EUI |
Direct unit injection |
EUI |
Governor Type |
Adem™A4 |
ADEM� A4 |
Generator Set Monitoring System (GMS) |
Adem™ A5 |
Generator Set Monitoring System (GMS) |
ADEM� A4 |
Generator Set Dimensions |
Length - Minimum |
164 in |
262.5 in |
- |
- |
- |
242.77 in |
Length - Maximum |
176.6 in |
331.1 in |
404 in |
311.9 in |
404 in |
320 in |
Width - Minimum |
66.3 in |
92 in |
- |
- |
- |
82.7 in |
Width - Maximum |
87.8 in |
128.5 in |
99.62 in |
104 in |
99.62 in |
122.8 in |
Height - Minimum |
85.1 in |
99.8 in |
- |
- |
- |
127.2 in |
Height - Maximum |
86.4 in |
150.7 in |
156.6 in |
131.6 in |
156.6 in |
142.3 in |
Dry Weight - Genset (minimum) |
14700 lb |
55100 lb |
- |
- |
- |
42750 lb |
Dry Weight - Genset (maximum) |
17855 lb |
66200 lb |
112690 lb |
40750 lb |
91050 lb |
45114 lb |