Compare Equipment Go Back

3412C | 800 kVA 50Hz Generator Set
C175-16 Generator Set

Generator Set Specifications

Maximum Rating 800 kVA 3365 ekW -
Minimum Rating 725 kVA 2500 ekW -
Emissions/Fuel Strategy Low Fuel Consumption Low Fuel, Tier 2 -
Voltage 380 to 415 Volts 480 to 13800 Volts -
Frequency 50 Hz 60 Hz -
Speed 1500 rpm 1800 RPM -
Duty Cycle Standby, Prime Standby, Mission Critical, Prime, Continuous -
Standby Rating - 3365(no fan)/3250/3100(no fan)/3000 ekW -
Prime Power Rating - 3115(no fan)/3000/2825(no fan)/2725 ekW -

Engine Specifications

Engine Model 3412C TA, V-12, 4-Stroke Water-Cooled Diesel C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel -
Bore 5.4 in 6.89 in -
Stroke 6 in 8.66 in -
Displacement 1648.86 in³ 6456.31 in³ -
Compression Ratio 13:01 16.7:1 -
Aspiration Turbocharged, Air to Air Aftercooled Turbo Aftercooled -
Fuel System Pump and Lines Common Rail -
Governor Type ADEM™ A5 ADEM� A4 -

Generator Set Dimensions

Length - Maximum 162.4 in 330.6 in -
Width - Minimum 75 in 82.7 in -
Width - Maximum 78.3 in 124.3 in -
Height - Maximum 75 in 134.2 in -
Dry Weight - Genset (minimum) 12039 lb 42750 lb -
Dry Weight - Genset (maximum) 13030 lb 57774 lb -
Length - Minimum - 250.9 in -
Height - Minimum - 86.9 in -
Add a Similar Product:
  • C280-16 Generator Set (Medium Speed) Add
  • 3616 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C280-6 Generator Set (Medium Speed) Add