C18 | DE715E0 50Hz LOW BSFC, LOW FUEL
C175-16 Tier 4 Final

Generator Set Specifications

Minimum Rating 650 kVA 2500 ekW 3150 ekW
Maximum Rating 715 kVA 3100 ekW 4000 ekW
Emissions/Fuel Strategy Non Regulated U.S. EPA Certified Tier 4 Low Fuel, Tier 2
Voltage 200 to 400 Volts 480 to 13800 Volts 480 to 13800 Volts
Frequency 50 Hz 60 Hz 60 Hz
Duty Cycle Standby, Prime Standby, Mission Critical, Prime, Continuous Standby, Mission Critical, Prime, Continuous
Standby Rating - 3100(no fan)/3000 ekW 4000 (no fan)/3900/3620(no fan)/3500 ekW
Prime Power Rating - 2825(no fan)/2725 ekW 3600 (no fan)/3500/3300 (no fan)/3180 ekW
Speed - 1800 rpm 1800 rpm

Engine Specifications

Aspiration Turbocharged, Air to Air Aftercooled Turbo Aftercooled Turbo Aftercooled
Engine Model - C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel
Bore - 6.89 in 6.89 in
Stroke - 8.66 in 8.66 in
Displacement - 5155.88 in³ 6456.31 in³
Compression Ratio - 16.7:1 15.3:1
Fuel System - EUI Common Rail
Governor Type - ADEM� A4 ADEM� A4

Generator Set Dimensions

Length - Minimum - 242.77 in 262.5 in
Length - Maximum - 320 in 331.1 in
Width - Minimum - 82.7 in 92 in
Width - Maximum - 122.8 in 128.5 in
Height - Minimum - 127.2 in 99.8 in
Height - Maximum - 142.3 in 150.7 in
Dry Weight - Genset (minimum) - 42750 lb 55100 lb
Dry Weight - Genset (maximum) - 45114 lb 66200 lb
Add a Similar Product:
  • C280-16 Generator Set (Medium Speed) Add
  • 3616 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C280-6 Generator Set (Medium Speed) Add
  • 3606 Generator Set (Medium Speed) Add