Compare Equipment Go Back

C2.2 | DE22E3 50Hz EU IIIA EMISSIONS COMPLIANT
3608 Generator Set (Medium Speed)
3606 Generator Set (Medium Speed)
C175-16 Generator Set
C175-16 Tier 4 Final
3516E Low Voltage Generator Set
3608 Generator Set (Medium Speed)

Generator Set Specifications

Minimum Rating 20 kVA 1830 ekW 3150 ekW 1775 kVA 2500 ekW 2500 ekW 2500 ekW 2363 kVA
Maximum Rating 22 kVA 2660 ekW 4000 ekW 2688 kVA 3365 ekW 3100 ekW 2750 ekW 3575 kVA
Emissions/Fuel Strategy R96/EUIIIa Equivalent Low Fuel Consumption Low Fuel, Tier 2 Low Fuel Consumption Low Fuel, Tier 2 U.S. EPA Certified Tier 4 Tier 2, Low NOx Low Fuel Consumption
Voltage 200 to 400 Volts - 480 to 13800 Volts - 480 to 13800 Volts 480 to 13800 Volts 416 to 13,800 Volts -
Frequency 50 Hz 60 Hz 60 Hz 50 Hz 60 Hz 60 Hz 60 Hz 50 Hz
Duty Cycle Standby, Prime Standby, Prime, Continuous Standby, Mission Critical, Prime, Continuous Continuous Standby, Mission Critical, Prime, Continuous Standby, Mission Critical, Prime, Continuous Standby, Mission Critical, Prime Standby, Prime, Continuous
Speed - 720 & 900 rpm 1800 rpm 750 & 1000 rpm 1800 RPM 1800 rpm 1800 rpm 750 & 1000 rpm
Standby Rating - - 4000 (no fan)/3900/3620(no fan)/3500 ekW - 3365(no fan)/3250/3100(no fan)/3000 ekW 3100(no fan)/3000 ekW 2750 ekW -
Prime Power Rating - - 3600 (no fan)/3500/3300 (no fan)/3180 ekW - 3115(no fan)/3000/2825(no fan)/2725 ekW 2825(no fan)/2725 ekW 2500 ekW -

Engine Specifications

Engine Model - 3608 I-8,4-Stroke Water-Cooled Diesel C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel 3606 I-6, 4-Stroke Water-Cooled Diesel C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel 3516E, V-16, 4-Stroke, Water-Cooled Diesel 3608 I-8,4-Stroke Water-Cooled Diesel
Bore - 11 in 6.89 in 11 in 6.89 in 6.89 in 6.69 in 11 in
Stroke - 11.8 in 8.66 in 11.8 in 8.66 in 8.66 in 8.47 in 11.8 in
Displacement - 9064 in³ 6456.31 in³ 6762 in³ 6456.31 in³ 5155.88 in³ 4765 in³ 9064 in³
Compression Ratio - 13:01 15.3:1 13:01 16.7:1 16.7:1 14.7:1 13:01
Aspiration - TA Turbo Aftercooled TA Turbo Aftercooled Turbo Aftercooled ATAAC TA
Fuel System - Direct unit injection Common Rail Direct unit injection Common Rail EUI EUI Direct unit injection
Governor Type - Generator Set Monitoring System (GMS) ADEM� A4 Generator Set Monitoring System (GMS) ADEM� A4 ADEM� A4 Adem™ A5 Generator Set Monitoring System (GMS)

Generator Set Dimensions

Length - Maximum - 404 in 331.1 in 404 in 330.6 in 320 in 311.9 in 404 in
Width - Maximum - 99.62 in 128.5 in 99.62 in 124.3 in 122.8 in 104 in 99.62 in
Height - Maximum - 156.6 in 150.7 in 156.6 in 134.2 in 142.3 in 131.6 in 156.6 in
Dry Weight - Genset (maximum) - 91050 lb 66200 lb 74970 lb 57774 lb 45114 lb 40750 lb 91050 lb
Length - Minimum - - 262.5 in - 250.9 in 242.77 in - -
Width - Minimum - - 92 in - 82.7 in 82.7 in - -
Height - Minimum - - 99.8 in - 86.9 in 127.2 in - -
Dry Weight - Genset (minimum) - - 55100 lb - 42750 lb 42750 lb - -
Add a Similar Product:
  • 3616 Generator Set (Medium Speed) Add
  • C280-16 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • C280-6 Generator Set (Medium Speed) Add
  • 3516E Low Voltage Generator Set Add
  • 3516E Generator Set Add
  • 3516E Generator Set Add