3512B Diesel Generator Set
C280-8 Generator Set (Medium Speed)
3608 Generator Set (Medium Speed)
C175-16 Tier 4 Final
C280-6 Generator Set (Medium Speed)
3612 Generator Set (Medium Speed)
3606 Generator Set (Medium Speed)

Generator Set Specifications

Standby Rating 1875/1750 kVA - - 3100(no fan)/3000 ekW - - 4000 (no fan)/3900/3620(no fan)/3500 ekW -
Prime Power Rating 1700/1600 kVA - - 2825(no fan)/2725 ekW - - 3600 (no fan)/3500/3300 (no fan)/3180 ekW -
Emissions/Fuel Strategy Low Fuel , Low Emissions EPA Tier 4 Final, IMO Tier 2 Low Fuel Consumption U.S. EPA Certified Tier 4 IMO Tier 2 Low Fuel Consumption Low Fuel, Tier 2 Low Fuel Consumption
Voltage 400 to 415 Volts - - 480 to 13800 Volts - - 480 to 13800 Volts -
Frequency 50 Hz 50 / 60 Hz 50 Hz 60 Hz 50 / 60 Hz 50 Hz 60 Hz 50 Hz
Speed 1500 rpm 900 / 1000 rpm 750 & 1000 rpm 1800 rpm 900 / 1000 rpm 750 & 1000 rpm 1800 rpm 750 & 1000 rpm
Duty Cycle Standby, Mission Critical, Prime, Continuous Prime, Continuous Standby, Prime, Continuous Standby, Mission Critical, Prime, Continuous Prime, Continuous Prime, Continuous Standby, Mission Critical, Prime, Continuous Continuous
Minimum Rating 1600 kVA 2200 ekW (60Hz), 2938 kVA (50Hz) 2363 kVA 2500 ekW 1650 ekW (60Hz), 2200 kVA (50Hz) 4400 kVA 3150 ekW 1775 kVA
Maximum Rating 1875 kVA 2420 ekW (60Hz), 3250 kVA (50Hz) 3575 kVA 3100 ekW 1820 ekW (60Hz), 2425 kVA (50Hz) 4850 kVA 4000 ekW 2688 kVA

Engine Specifications

Engine Model 3512B TA, V-12, 4-Stroke Water-Cooled Diesel C280-8, I-8,4-Stroke Water-Cooled Diesel 3608 I-8,4-Stroke Water-Cooled Diesel C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel C280-6, I-6,4-Stroke Water-Cooled Diesel 3612 V-12,4-Stroke Water-Cooled Diesel C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel 3606 I-6, 4-Stroke Water-Cooled Diesel
Bore 6.69 in 11 in 11 in 6.89 in 11 in 11 in 6.89 in 11 in
Stroke 7.48 in 11.8 in 11.8 in 8.66 in 11.8 in 11.8 in 8.66 in 11.8 in
Stroke - HD 8.46 in - - - - - - -
Displacement 3161.03 in³ 9064 in³ 9064 in³ 5155.88 in³ 111 in³ 13524 in³ 6456.31 in³ 6762 in³
Displacement - HD 3576 in³ - - - - - - -
Compression Ratio 15.5:1 HD 13:01 13:01 16.7:1 13:01 13:01 15.3:1 13:01
Aspiration TA TA TA Turbo Aftercooled TA TA Turbo Aftercooled TA
Fuel System Electronic Unit Injection Direct unit injection Direct unit injection EUI Direct unit injection Direct unit injection Common Rail Direct unit injection
Governor Type ADEM™ A3 Generator Set Monitoring System (GMS) Generator Set Monitoring System (GMS) ADEM� A4 Generator Set Monitoring System (GMS) Generator Set Monitoring System (GMS) ADEM� A4 Generator Set Monitoring System (GMS)

Generator Set Dimensions

Length - Minimum 212.8 in - - 242.77 in - - 262.5 in -
Length - Maximum 217.1 in 404 in 404 in 320 in 404 in 404 in 331.1 in 404 in
Width - Minimum 90 in - - 82.7 in - - 92 in -
Width - Maximum 90 in 99.62 in 99.62 in 122.8 in 99.62 in 99.62 in 128.5 in 99.62 in
Height - Minimum 94.9 in - - 127.2 in - - 99.8 in -
Height - Maximum 94.9 in 156.6 in 156.6 in 142.3 in 156.6 in 156.6 in 150.7 in 156.6 in
Dry Weight - Genset (minimum) 25620 lb - - 42750 lb - - 55100 lb -
Dry Weight - Genset (maximum) 26530 lb 91050 lb 91050 lb 45114 lb 74970 lb 112690 lb 66200 lb 74970 lb
Add a Similar Product:
  • 3616 Generator Set (Medium Speed) Add
  • C280-16 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C175-16 Generator Set Add
  • 3516E Generator Set Add
  • 3516E Low Voltage Generator Set Add
  • 3516E Low Voltage Generator Set Add
  • 3516E Generator Set Add