Compare Equipment Go Back

3512B Diesel Generator Set
C175-16 Generator Set
C175-16 Tier 4 Final
3516E Generator Set

Generator Set Specifications

Standby Rating 1875/1750 kVA 3365(no fan)/3250/3100(no fan)/3000 ekW 4000 (no fan)/3900/3620(no fan)/3500 ekW 3100(no fan)/3000 ekW 3500/3250/3000 kVA
Prime Power Rating 1700/1600 kVA 3115(no fan)/3000/2825(no fan)/2725 ekW 3600 (no fan)/3500/3300 (no fan)/3180 ekW 2825(no fan)/2725 ekW 3175/2950/2725 kVA
Emissions/Fuel Strategy Low Fuel , Low Emissions Low Fuel, Tier 2 Low Fuel, Tier 2 U.S. EPA Certified Tier 4 U.S. EPA Cert. Tier 2 / Low NOx
Voltage 400 to 415 Volts 480 to 13800 Volts 480 to 13800 Volts 480 to 13800 Volts 380 to 11000 volts
Frequency 50 Hz 60 Hz 60 Hz 60 Hz 50 Hz
Speed 1500 rpm 1800 RPM 1800 rpm 1800 rpm 1500 rpm
Duty Cycle Standby, Mission Critical, Prime, Continuous Standby, Mission Critical, Prime, Continuous Standby, Mission Critical, Prime, Continuous Standby, Mission Critical, Prime, Continuous Standby, Mission Critical, Prime
Minimum Rating 1600 kVA 2500 ekW 3150 ekW 2500 ekW 2725 kVA
Maximum Rating 1875 kVA 3365 ekW 4000 ekW 3100 ekW 3500 kVA

Engine Specifications

Engine Model 3512B TA, V-12, 4-Stroke Water-Cooled Diesel C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel 3516E, V-16, 4-Stroke Water-Cooled Diesel
Bore 6.69 in 6.89 in 6.89 in 6.89 in 6.69 in
Stroke 7.48 in 8.66 in 8.66 in 8.66 in 8.46 in
Stroke - HD 8.46 in - - - -
Displacement 3161.03 in³ 6456.31 in³ 6456.31 in³ 5155.88 in³ 4765 in³
Displacement - HD 3576 in³ - - - -
Compression Ratio 15.5:1 HD 16.7:1 15.3:1 16.7:1 14.0:1
Aspiration TA Turbo Aftercooled Turbo Aftercooled Turbo Aftercooled ATAAC
Fuel System Electronic Unit Injection Common Rail Common Rail EUI Electronic Unit Injection
Governor Type ADEM™ A3 ADEM� A4 ADEM� A4 ADEM� A4 Adem™ A5

Generator Set Dimensions

Length - Minimum 212.8 in 250.9 in 262.5 in 242.77 in 313.4 in
Length - Maximum 217.1 in 330.6 in 331.1 in 320 in 318.4 in
Width - Minimum 90 in 82.7 in 92 in 82.7 in 104 in
Width - Maximum 90 in 124.3 in 128.5 in 122.8 in 104 in
Height - Minimum 94.9 in 86.9 in 99.8 in 127.2 in 131.6 in
Height - Maximum 94.9 in 134.2 in 150.7 in 142.3 in 131.6 in
Dry Weight - Genset (minimum) 25620 lb 42750 lb 55100 lb 42750 lb 44930 lb
Dry Weight - Genset (maximum) 26530 lb 57774 lb 66200 lb 45114 lb 45651 lb
Add a Similar Product:
  • 3616 Generator Set (Medium Speed) Add
  • C280-16 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • C280-6 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3606 Generator Set (Medium Speed) Add