3512B Diesel Generator Set
C175-16 Generator Set
3516E Generator Set
3612 Generator Set (Medium Speed)

Generator Set Specifications

Standby Rating 1875/1750 kVA 3365(no fan)/3250/3100(no fan)/3000 ekW 3500/3250/3000 kVA - 4000 (no fan)/3900/3620(no fan)/3500 ekW
Prime Power Rating 1700/1600 kVA 3115(no fan)/3000/2825(no fan)/2725 ekW 3175/2950/2725 kVA - 3600 (no fan)/3500/3300 (no fan)/3180 ekW
Emissions/Fuel Strategy Low Fuel , Low Emissions Low Fuel, Tier 2 U.S. EPA Cert. Tier 2 / Low NOx Low Fuel Consumption Low Fuel, Tier 2
Voltage 400 to 415 Volts 480 to 13800 Volts 380 to 11000 volts - 480 to 13800 Volts
Frequency 50 Hz 60 Hz 50 Hz 50 Hz 60 Hz
Speed 1500 rpm 1800 RPM 1500 rpm 750 & 1000 rpm 1800 rpm
Duty Cycle Standby, Mission Critical, Prime, Continuous Standby, Mission Critical, Prime, Continuous Standby, Mission Critical, Prime Prime, Continuous Standby, Mission Critical, Prime, Continuous
Minimum Rating 1600 kVA 2500 ekW 2725 kVA 4400 kVA 3150 ekW
Maximum Rating 1875 kVA 3365 ekW 3500 kVA 4850 kVA 4000 ekW

Engine Specifications

Engine Model 3512B TA, V-12, 4-Stroke Water-Cooled Diesel C175-16 SCAC, V-16, 4-Stroke Water-Cooled Diesel 3516E, V-16, 4-Stroke Water-Cooled Diesel 3612 V-12,4-Stroke Water-Cooled Diesel C175-20 SCAC, V-20, 4-Stroke Water-Cooled Diesel
Bore 6.69 in 6.89 in 6.69 in 11 in 6.89 in
Stroke 7.48 in 8.66 in 8.46 in 11.8 in 8.66 in
Stroke - HD 8.46 in - - - -
Displacement 3161.03 in³ 6456.31 in³ 4765 in³ 13524 in³ 6456.31 in³
Displacement - HD 3576 in³ - - - -
Compression Ratio 15.5:1 HD 16.7:1 14.0:1 13:01 15.3:1
Aspiration TA Turbo Aftercooled ATAAC TA Turbo Aftercooled
Fuel System Electronic Unit Injection Common Rail Electronic Unit Injection Direct unit injection Common Rail
Governor Type ADEM™ A3 ADEM� A4 Adem™ A5 Generator Set Monitoring System (GMS) ADEM� A4

Generator Set Dimensions

Length - Minimum 212.8 in 250.9 in 313.4 in - 262.5 in
Length - Maximum 217.1 in 330.6 in 318.4 in 404 in 331.1 in
Width - Minimum 90 in 82.7 in 104 in - 92 in
Width - Maximum 90 in 124.3 in 104 in 99.62 in 128.5 in
Height - Minimum 94.9 in 86.9 in 131.6 in - 99.8 in
Height - Maximum 94.9 in 134.2 in 131.6 in 156.6 in 150.7 in
Dry Weight - Genset (minimum) 25620 lb 42750 lb 44930 lb - 55100 lb
Dry Weight - Genset (maximum) 26530 lb 57774 lb 45651 lb 112690 lb 66200 lb
Add a Similar Product:
  • C280-16 Generator Set (Medium Speed) Add
  • 3616 Generator Set (Medium Speed) Add
  • C280-12 Generator Set (Medium Speed) Add
  • 3612 Generator Set (Medium Speed) Add
  • C280-8 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • 3608 Generator Set (Medium Speed) Add
  • C280-6 Generator Set (Medium Speed) Add
  • 3606 Generator Set (Medium Speed) Add
  • C175-16 Tier 4 Final Add