DG400 (3-Phase)
EMCP 4.4 Master Control Panel

Generator Set Specifications

Frequency 60 Hz - -
Natural Gas Rating 400 ekW - -
Emissions/Fuel Strategy U.S. EPA Certified for Stationary Emergency Application and Non-Emergency Applications - -
RPM 1800 - -
Fuel Type Natural Gas - -
Voltage 208 - 600 VAC - -

Engine Specifications

Engine Model Cat® CG18 In-line 6, 4-cycle Natural Gas - -
Fuel System Gas mixer, Venturi - -
Aspiration Turbocharged - Air-to-Air Aftercooled - -
Governor Type Electronic - -
Displacement 1106.3 in³ - -
Compression Ratio 10.5:1 - -
Bore 5.7 in - -
Stroke 7.2 in - -

Generator Set Dimensions

Length 154 in - -
Width 73 in - -
Height 82 in - -
Weight 10721 lb - -

Technical Summary

Configuration - Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source. -
Modes of Operation - Emergency standby, island, utility paralleling -
Application - LV and MV (208V - 38 kV) -

Generator Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 -

Utility Protective Devices

ANSI Protective Devices - 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) -

Environmental Parameters

Certifications - IBC, CBC, UBC & OSHPD Certified -
Control Panel Enclosure - NEMA 1 wall-mounted construction -
Operating Temperature - 0°C to 50°C -
Storage Temperature - -20°C to +60°C -
Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 -
Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 -
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Cat Switchgear Add
  • Cat EGP Switchgear Add
  • Cat XLM Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Capacity Expansion (ECE) module Add
  • Energy Time Shift (ETS) Module Add
  • Temporary Connection Boxes Add