Compare Equipment Go Back
DG350 (3-Phase) |
Engine Paralleling and Integration Control (EPIC) |
Cat XLM Switchgear |
XQ425 |
|
Generator Set Specifications |
||||
---|---|---|---|---|
Frequency | 60 Hz | - | - | - |
Natural Gas Rating | 350 ekW | - | - | - |
Emissions/Fuel Strategy | U.S. EPA Certified for Stationary Emergency Application and Non-Emergency Applications | - | - | - |
Fuel Type | Natural Gas | - | - | - |
RPM | 1800 | - | - | - |
Voltage | 208 - 600 VAC | - | - | - |
Engine Specifications |
||||
Engine Model | Cat® CG18 In-line 6, 4-cycle Natural Gas | - | - | - |
Fuel System | Gas mixer, Venturi | - | - | - |
Aspiration | Turbocharged - Air-to-Air Aftercooled | - | - | - |
Governor Type | Electronic | - | - | - |
Displacement | 1106.3 in³ | - | - | - |
Compression Ratio | 10.5:1 | - | - | - |
Bore | 5.7 in | - | - | - |
Stroke | 7.2 in | - | - | - |
Generator Set Dimensions |
||||
Length | 154 in | - | - | - |
Width | 73 in | - | - | - |
Height | 82 in | - | - | - |
Weight | 10721 lb | - | - | - |
Technical Summary |
||||
Configuration | - | Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications | - |
Modes of Operation | - | Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) | Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power | - |
Application | - | LV and MV (208V-27kV) | LV and MV ( 208V - 38 kV | - |
Generator Protective Devices |
||||
ANSI Protective Devices | - | 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | - |
Utility Protective Devices |
||||
ANSI Protective Devices | - | 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) | 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 | - |
Environmental Parameters |
||||
Certifications | - | UL / cUL 508A | IBS, CBC, UBC & OSHPD Certified | - |
Control Panel Enclosure | - | NEMA 12 | NEMA 1 or NEMA 3R, Freestanding Construction | - |
Operating Temperature | - | 0°C to 55°C | 0 degrees to 50 degrees C | - |
Storage Temperature | - | -20°C to 60°C | -20 degrees C to +60 degrees C | - |
Low Voltage Standards | - | - | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | - |
Medium Voltage Standards | - | - | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | - |
Generator Set |
||||
Rating Prime | - | - | - | 340 ekW (425 kVA) |
Frequency | - | - | - | 50/60 Hz |
Voltage | - | - | - | 120 - 600 V |
Rating Standby | - | - | - | 375 ekW (469 kVA) |
Engine |
||||
Engine | - | - | - | C13 |
Fuel | - | - | - | Diesel |
Dimensions |
||||
Height - Without Trailer | - | - | - | 60 in |
Length - Without Trailer | - | - | - | 208.7 in |
Width - Without Trailer | - | - | - | 104 in |
Weight with Lube Oil and Coolant, Without Trailer | - | - | - | 14700 lb |
Fuel Consumption |
||||
100% Load 60Hz | - | - | - | 25.1 gal/hr |
75% Load 60Hz | - | - | - | 19.2 gal/hr |
50% Load 60Hz | - | - | - | 13.6 gal/hr |
Noise rating (with enclosure) |
||||
Sound Power @ 7 meters (23 feet) @ All Ratings | - | - | - | 74 dB(A) |
Add a Similar Product:
-
Cat Customizable Switchgear and Controls Add
-
Cat Switchgear Add
-
Cat EGP Switchgear Add
-
EMCP 4.4 Master Control Panel Add
-
Cat® BDP1000 Bi-Directional Power Inverter Add
-
XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
-
Temporary Connection Boxes Add
-
XQP550 EU Stage V Add
-
XQ230 Rental Power Add
-
XQ125 Rental Power Add