Compare Equipment Go Back

DG350 (3-Phase)
XQ570 Tier 4 Final - 455 ekW (568 kVA)

Generator Set Specifications

Frequency 60 Hz - -
Natural Gas Rating 350 ekW - -
Emissions/Fuel Strategy U.S. EPA Certified for Stationary Emergency Application and Non-Emergency Applications - -
Fuel Type Natural Gas - -
RPM 1800 - -
Voltage 208 - 600 VAC - -

Engine Specifications

Engine Model Cat® CG18 In-line 6, 4-cycle Natural Gas - -
Fuel System Gas mixer, Venturi - -
Aspiration Turbocharged - Air-to-Air Aftercooled - -
Governor Type Electronic - -
Displacement 1106.3 in³ - -
Compression Ratio 10.5:1 - -
Bore 5.7 in - -
Stroke 7.2 in - -

Generator Set Dimensions

Length 154 in - -
Width 73 in - -
Height 82 in - -
Weight 10721 lb - -

Generator Set

Rating Prime - 455 ekW (568 kVA) -
Frequency - 60 Hz -
Voltage - 120 - 600 V -
Rating Standby - 500 ekW (625 kVA) -

Engine

Engine - Cat C18 -
Fuel - Diesel -

Dimensions

Height - Without Trailer - 102 in -
Length - Without Trailer - 240 in -
Width - Without Trailer - 96 in -
Weight with Lube Oil and Coolant, Without Trailer - 24125 lb -

Fuel Consumption

100% Load 60Hz - 35.9 gal/hr -
75% Load 60Hz - 28.3 gal/hr -
50% Load 60Hz - 20.5 gal/hr -

Noise rating (with enclosure)

Sound Power @ 7 meters (23 feet) @ All Ratings - 74 dB(A) -
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Cat Switchgear Add
  • Cat XLM Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Cat EGP Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Temporary Connection Boxes Add
  • XQ425 Add
  • XQP550 EU Stage V Add