Compare Equipment Go Back
DG350 (3-Phase) |
Cat® BDP1000 Bi-Directional Power Inverter |
Cat XLM Switchgear |
EMCP 4.4 Master Control Panel |
XQP550 EU Stage V |
|
Generator Set Specifications |
|||||
---|---|---|---|---|---|
Frequency | 60 Hz | - | - | - | - |
Natural Gas Rating | 350 ekW | - | - | - | - |
Emissions/Fuel Strategy | U.S. EPA Certified for Stationary Emergency Application and Non-Emergency Applications | - | - | - | - |
Fuel Type | Natural Gas | - | - | - | - |
RPM | 1800 | - | - | - | - |
Voltage | 208 - 600 VAC | - | - | - | - |
Engine Specifications |
|||||
Engine Model | Cat® CG18 In-line 6, 4-cycle Natural Gas | - | - | - | - |
Fuel System | Gas mixer, Venturi | - | - | - | - |
Aspiration | Turbocharged - Air-to-Air Aftercooled | - | - | - | - |
Governor Type | Electronic | - | - | - | - |
Displacement | 1106.3 in³ | - | - | - | - |
Compression Ratio | 10.5:1 | - | - | - | - |
Bore | 5.7 in | - | - | - | - |
Stroke | 7.2 in | - | - | - | - |
Generator Set Dimensions |
|||||
Length | 154 in | - | - | - | - |
Width | 73 in | - | - | - | - |
Height | 82 in | - | - | - | - |
Weight | 10721 lb | - | - | - | - |
Technical Summary |
|||||
Application | - | Energy Storage System | LV and MV ( 208V - 38 kV | LV and MV (208V - 38 kV) | - |
Module Type | - | Integral part of Power Grid Stabilization and Energy Time Shift modules | - | - | - |
Rated Power | - | 1000 kVA (1000kW 1PF) | - | - | - |
Configuration | - | - | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications | Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source. | - |
Modes of Operation | - | - | Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power | Emergency standby, island, utility paralleling | - |
Generator Protective Devices |
|||||
ANSI Protective Devices | - | - | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | - |
Utility Protective Devices |
|||||
ANSI Protective Devices | - | - | 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 | 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) | - |
Environmental Parameters |
|||||
Certifications | - | - | IBS, CBC, UBC & OSHPD Certified | IBC, CBC, UBC & OSHPD Certified | - |
Control Panel Enclosure | - | - | NEMA 1 or NEMA 3R, Freestanding Construction | NEMA 1 wall-mounted construction | - |
Operating Temperature | - | - | 0 degrees to 50 degrees C | 0°C to 50°C | - |
Storage Temperature | - | - | -20 degrees C to +60 degrees C | -20°C to +60°C | - |
Low Voltage Standards | - | - | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | - |
Medium Voltage Standards | - | - | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | - |
Generator Set |
|||||
Rating Prime | - | - | - | - | 550 kVA |
Frequency | - | - | - | - | 50/60 Hz |
Voltage | - | - | - | - | 220 - 480 V |
Fuel/Emissions Strategy | - | - | - | - | EU Stage V |
Engine |
|||||
Engine | - | - | - | - | Cat® C18 |
Fuel | - | - | - | - | Diesel |
Dimensions |
|||||
Width | - | - | - | - | 80.3 in |
Height | - | - | - | - | 90.5 in |
Length | - | - | - | - | 213.3 in |
Weight - With Lube Oil and Coolant | - | - | - | - | 14860 lb |
Fuel Consumption |
|||||
100% Load 60 Hz | - | - | - | - | 34.3 gal/hr |
100% Load 50 Hz | - | - | - | - | 33.4 gal/hr |
75% Load 60 Hz | - | - | - | - | 26.13 gal/hr |
75% Load 50 Hz | - | - | - | - | 24.9 gal/hr |
Noise rating (with enclosure) |
|||||
Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz) | - | - | - | - | 79.19 |
Add a Similar Product: