Cat® BDP1000 Bi-Directional Power Inverter
|
Engine Paralleling and Integration Control (EPIC)
|
Generator Set Specifications |
Frequency |
60 Hz |
- |
- |
Natural Gas Rating |
350 ekW |
- |
- |
Emissions/Fuel Strategy |
U.S. EPA Certified for Stationary Emergency Application and Non-Emergency Applications |
- |
- |
Fuel Type |
Natural Gas |
- |
- |
RPM |
1800 |
- |
- |
Voltage |
208 - 600 VAC |
- |
- |
Engine Specifications |
Engine Model |
Cat® CG18 In-line 6, 4-cycle Natural
Gas |
- |
- |
Fuel System |
Gas mixer, Venturi |
- |
- |
Aspiration |
Turbocharged - Air-to-Air Aftercooled |
- |
- |
Governor Type |
Electronic |
- |
- |
Displacement |
1106.3 in³ |
- |
- |
Compression Ratio |
10.5:1 |
- |
- |
Bore |
5.7 in |
- |
- |
Stroke |
7.2 in |
- |
- |
Generator Set Dimensions |
Length |
154 in |
- |
- |
Width |
73 in |
- |
- |
Height |
82 in |
- |
- |
Weight |
10721 lb |
- |
- |
Technical Summary |
Application |
- |
Energy Storage System |
LV and MV (208V-27kV) |
Module Type |
- |
Integral part of Power Grid Stabilization and Energy Time Shift modules |
- |
Rated Power |
- |
1000 kVA (1000kW 1PF) |
- |
Configuration |
- |
- |
Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) |
Modes of Operation |
- |
- |
Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) |
Generator Protective Devices |
ANSI Protective Devices |
- |
- |
15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) |
Utility Protective Devices |
ANSI Protective Devices |
- |
- |
15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) |
Environmental Parameters |
Certifications |
- |
- |
UL / cUL 508A |
Control Panel Enclosure |
- |
- |
NEMA 12 |
Operating Temperature |
- |
- |
0°C to 55°C |
Storage Temperature |
- |
- |
-20°C to 60°C |