CG260-16 Gas Generator Set |
Cat Customizable Switchgear and Controls |
Cat EGP Switchgear |
|
Generator Set Specifications |
|||
---|---|---|---|
Continuous Rating | 4500 / 4050 ekW @1.0pf | - | - |
Fuel Type | Natural Gas, Hydrogen Blend (up to 10%) | - | - |
Maximum Electrical Efficiency | 44.60 / 44.3% | - | - |
Maximum Standby Rating | 4500 ekW | - | - |
Frequency | 50 / 60 Hz | - | - |
RPM | 1000 / 900 rpm | - | - |
Generator Set Dimensions |
|||
Length | 371 in | - | - |
Width | 110 in | - | - |
Height | 133 in | - | - |
Dry Weight - Genset | 117505 lb | - | - |
Engine Specifications |
|||
Engine Model | CG260-16 | - | - |
Displacement | 16586 in³ | - | - |
Stroke | 12.6 in | - | - |
Bore | 10.2 in | - | - |
Aspiration | TA | - | - |
Technical Summary |
|||
Configuration | - | Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications |
Modes of Operation | - | All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow | Multi-unit Island and multi-unit standby mode with optional redundant controls and components. |
Application | - | LV and MV ( 208V - 38 kV) 50 / 60 Hz | LV and MV (208V - 38 kV) |
Generator Protective Devices |
|||
ANSI Protective Devices | - | Per customer specification | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 |
Utility Protective Devices |
|||
ANSI Protective Devices | - | Per customer specification | - |
Environmental Parameters |
|||
Certifications | - | Per customer specification | IBC, CBC, UBC & OSHPD Certified |
Control Panel Enclosure | - | Per customer specification | NEMA 1 or NEMA 3R Freestanding Construction |
Operating Temperature | - | Per customer specification | 0°C to 50°C |
Storage Temperature | - | Per customer specification | -20°C to +60°C |
Low Voltage Standards | - | Per customer specification | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 |
Medium Voltage Standards | - | Per customer specification | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 |
Add a Similar Product:
- Cat Switchgear Add
- Cat XLM Switchgear Add
- EMCP 4.4 Master Control Panel Add
- Engine Paralleling and Integration Control (EPIC) Add
- Energy Time Shift (ETS) Module Add
- Energy Capacity Expansion (ECE) module Add
- Cat® BDP1000 Bi-Directional Power Inverter Add
- XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
- Temporary Connection Boxes Add
- XQ425 Add