CG260-16 Gas Generator Set |
Cat Customizable Switchgear and Controls |
Engine Paralleling and Integration Control (EPIC) |
Cat XLM Switchgear |
|
Generator Set Specifications |
||||
---|---|---|---|---|
Continuous Rating | 4500 / 4050 ekW @1.0pf | - | - | - |
Fuel Type | Natural Gas, Hydrogen Blend (up to 25%) | - | - | - |
Maximum Electrical Efficiency | 44.60 / 44.3% | - | - | - |
Maximum Standby Rating | 4500 ekW | - | - | - |
Frequency | 50 / 60 Hz | - | - | - |
RPM | 1000 / 900 rpm | - | - | - |
Generator Set Dimensions |
||||
Length | 371 in | - | - | - |
Width | 110 in | - | - | - |
Height | 133 in | - | - | - |
Dry Weight - Genset | 117505 lb | - | - | - |
Engine Specifications |
||||
Engine Model | CG260-16 | - | - | - |
Displacement | 16586 in³ | - | - | - |
Stroke | 12.6 in | - | - | - |
Bore | 10.2 in | - | - | - |
Aspiration | TA | - | - | - |
Technical Summary |
||||
Configuration | - | Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc | Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications |
Modes of Operation | - | All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow | Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) | Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power |
Application | - | LV and MV ( 208V - 38 kV) 50 / 60 Hz | LV and MV (208V-27kV) | LV and MV ( 208V - 38 kV |
Generator Protective Devices |
||||
ANSI Protective Devices | - | Per customer specification | 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 |
Utility Protective Devices |
||||
ANSI Protective Devices | - | Per customer specification | 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) | 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 |
Environmental Parameters |
||||
Certifications | - | Per customer specification | UL / cUL 508A | IBS, CBC, UBC & OSHPD Certified |
Control Panel Enclosure | - | Per customer specification | NEMA 12 | NEMA 1 or NEMA 3R, Freestanding Construction |
Operating Temperature | - | Per customer specification | 0°C to 55°C | 0 degrees to 50 degrees C |
Storage Temperature | - | Per customer specification | -20°C to 60°C | -20 degrees C to +60 degrees C |
Low Voltage Standards | - | Per customer specification | - | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 |
Medium Voltage Standards | - | Per customer specification | - | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 |
Add a Similar Product:
- Cat Switchgear Add
- Cat EGP Switchgear Add
- EMCP 4.4 Master Control Panel Add
- Cat® BDP1000 Bi-Directional Power Inverter Add
- Energy Capacity Expansion (ECE) module Add
- Energy Time Shift (ETS) Module Add
- XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
- Temporary Connection Boxes Add
- XQP550 EU Stage V Add