CG260-16 Gas Generator Set
|
|
Engine Paralleling and Integration Control (EPIC)
|
Cat Customizable Switchgear and Controls
|
Generator Set Specifications |
Continuous Rating |
4500 / 4050 ekW @1.0pf |
- |
- |
- |
Fuel Type |
Natural Gas, Hydrogen Blend (up to 25%) |
- |
- |
- |
Maximum Electrical Efficiency |
44.60 / 44.3% |
- |
- |
- |
Maximum Standby Rating |
4500 ekW |
- |
- |
- |
Frequency |
50 / 60 Hz |
- |
- |
- |
RPM |
1000 / 900 rpm |
- |
- |
- |
Generator Set Dimensions |
Length |
371 in |
- |
- |
- |
Width |
110 in |
- |
- |
- |
Height |
133 in |
- |
- |
- |
Dry Weight - Genset |
117505 lb |
- |
- |
- |
Engine Specifications |
Engine Model |
CG260-16 |
- |
- |
- |
Displacement |
16586 in³ |
- |
- |
- |
Stroke |
12.6 in |
- |
- |
- |
Bore |
10.2 in |
- |
- |
- |
Aspiration |
TA |
- |
- |
- |
Technical Summary |
Configuration |
- |
Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications |
Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) |
Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc |
Modes of Operation |
- |
Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power |
Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) |
All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow |
Application |
- |
LV and MV ( 208V - 38 kV |
LV and MV (208V-27kV) |
LV and MV ( 208V - 38 kV) 50 / 60 Hz |
Generator Protective Devices |
ANSI Protective Devices |
- |
15/25, 27/59, 81 O/U, 32, 40, 50, 51 |
15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) |
Per customer specification |
Utility Protective Devices |
ANSI Protective Devices |
- |
15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 |
15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) |
Per customer specification |
Environmental Parameters |
Certifications |
- |
IBS, CBC, UBC & OSHPD Certified |
UL / cUL 508A |
Per customer specification |
Control Panel Enclosure |
- |
NEMA 1 or NEMA 3R, Freestanding Construction |
NEMA 12 |
Per customer specification |
Operating Temperature |
- |
0 degrees to 50 degrees C |
0°C to 55°C |
Per customer specification |
Storage Temperature |
- |
-20 degrees C to +60 degrees C |
-20°C to 60°C |
Per customer specification |
Low Voltage Standards |
- |
NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 |
- |
Per customer specification |
Medium Voltage Standards |
- |
NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 |
- |
Per customer specification |