CG260-16 Gas Generator Set
|
|
Engine Paralleling and Integration Control (EPIC)
|
XQ570 Tier 4 Final - 455 ekW (568 kVA)
|
|
|
Generator Set Specifications |
Continuous Rating |
4500 / 4050 ekW @1.0pf |
- |
- |
- |
- |
- |
Fuel Type |
Natural Gas, Hydrogen Blend (up to 25%) |
- |
- |
- |
- |
- |
Maximum Electrical Efficiency |
44.60 / 44.3% |
- |
- |
- |
- |
- |
Maximum Standby Rating |
4500 ekW |
- |
- |
- |
- |
- |
Frequency |
50 / 60 Hz |
- |
- |
- |
- |
- |
RPM |
1000 / 900 rpm |
- |
- |
- |
- |
- |
Generator Set Dimensions |
Length |
371 in |
- |
- |
- |
- |
- |
Width |
110 in |
- |
- |
- |
- |
- |
Height |
133 in |
- |
- |
- |
- |
- |
Dry Weight - Genset |
117505 lb |
- |
- |
- |
- |
- |
Engine Specifications |
Engine Model |
CG260-16 |
- |
- |
- |
- |
- |
Displacement |
16586 in³ |
- |
- |
- |
- |
- |
Stroke |
12.6 in |
- |
- |
- |
- |
- |
Bore |
10.2 in |
- |
- |
- |
- |
- |
Aspiration |
TA |
- |
- |
- |
- |
- |
Technical Summary |
Configuration |
- |
Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications |
Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) |
- |
- |
- |
Modes of Operation |
- |
Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power |
Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) |
- |
- |
- |
Application |
- |
LV and MV ( 208V - 38 kV |
LV and MV (208V-27kV) |
- |
- |
- |
Generator Protective Devices |
ANSI Protective Devices |
- |
15/25, 27/59, 81 O/U, 32, 40, 50, 51 |
15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) |
- |
- |
- |
Utility Protective Devices |
ANSI Protective Devices |
- |
15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 |
15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) |
- |
- |
- |
Environmental Parameters |
Certifications |
- |
IBS, CBC, UBC & OSHPD Certified |
UL / cUL 508A |
- |
- |
- |
Control Panel Enclosure |
- |
NEMA 1 or NEMA 3R, Freestanding Construction |
NEMA 12 |
- |
- |
- |
Operating Temperature |
- |
0 degrees to 50 degrees C |
0°C to 55°C |
- |
- |
- |
Storage Temperature |
- |
-20 degrees C to +60 degrees C |
-20°C to 60°C |
- |
- |
- |
Low Voltage Standards |
- |
NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 |
- |
- |
- |
- |
Medium Voltage Standards |
- |
NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 |
- |
- |
- |
- |
Generator Set |
Rating Prime |
- |
- |
- |
455 ekW (568 kVA) |
340 ekW (425 kVA) |
47.5 ekW (60 kVA) |
Frequency |
- |
- |
- |
60 Hz |
50/60 Hz |
60 Hz |
Voltage |
- |
- |
- |
120 - 600 V |
120 - 600 V |
120 - 600 V |
Rating Standby |
- |
- |
- |
500 ekW (625 kVA) |
375 ekW (469 kVA) |
- |
Engine |
Engine |
- |
- |
- |
Cat C18 |
C13 |
Cat C3.4 |
Fuel |
- |
- |
- |
Diesel |
Diesel |
Diesel |
Dimensions |
Height - Without Trailer |
- |
- |
- |
102 in |
60 in |
65.3 in |
Length - Without Trailer |
- |
- |
- |
240 in |
208.7 in |
106.5 in |
Width - Without Trailer |
- |
- |
- |
96 in |
104 in |
41.3 in |
Weight with Lube Oil and Coolant, Without Trailer |
- |
- |
- |
24125 lb |
14700 lb |
1305 kg |
Fuel Consumption |
100% Load 60Hz |
- |
- |
- |
35.9 gal/hr |
25.1 gal/hr |
3.7 gal/hr |
75% Load 60Hz |
- |
- |
- |
28.3 gal/hr |
19.2 gal/hr |
2.8 gal/hr |
50% Load 60Hz |
- |
- |
- |
20.5 gal/hr |
13.6 gal/hr |
1.9 gal/hr |
Noise rating (with enclosure) |
Sound Power @ 7 meters (23 feet) @ All Ratings |
- |
- |
- |
74 dB(A) |
74 dB(A) |
63 dB(A) |